Bulletin 700S-CF
Safety Control Relays
6
Specifications, Continued
Control Circuit
➊
For 9V DC, code ZR, use operating voltage 0.65… 1.3 x U
s
.
For 24V DC, code ZJ or DJ, use operating voltage 0.7… 1.25 x U
s
.
General
➋
8 kV for main poles, 6 kV for front aux. contacts.
➌
40 degree max. for 700S-CF350 with DC coil.
➍
Operation in 70°C ambient is permitted with current reduction of 15%
below rated values
Cat. No.
700S-CF
Operating Voltage
AC 50/60
Hz
Pickup
[x U
s
]
0.85…1.1
Dropout
[x U
s
]
0.3…0.6
DC
➊
Pickup
[x U
s
]
0.8…1.1
Dropout
[x U
s
]
0.1…0.6
Coil Consumption at nominal voltage
AC 50/60
Hz
Inrush
[VA/W]
70/50
Seal [VA/W]
8/2.6
DC
Inrush/Seal
warm coil
[W]
6.5
Inrush/Seal
cold coil
[W]
8.5
Operating Times
AC 50/60
Hz
Pickup Time
[ms]
15…30
Dropout Time
[ms
]
10…60
DC
Pickup Time
[ms]
40…70
Dropout Time
[ms
]
7…15
With integrated suppression
[ms
]
14…20
With diode
suppression
[ms
]
70…95
Cat. No. 700S-CF
Rated Insulation Voltage
U
i
IEC
690V
UL; CSA
600V
Dielectric Withstand Voltage
2500V
Rated Impulse Strength
U
imp
8 kV
➋
Rated Voltage
U
e
AC
115, 230, 400, 500, 690V
DC
24, 48, 110, 220, 440V
Short-Circuit Protection IEC 947-5
Fuse-Type GG
20 A
Rated Frequency
50/60 Hz, DC
Ambient Temperature
Storage
–55…+80
°
C (–67…176
°
F)
Operation at nominal current
–25…+60
°
C (–13…140
°
F)
➌➍
Corrosion Resistance
humid-alternating climate,
cyclic, per IEC 68-2-30 and
DIN 50 016, 56 cycles
Altitude
2000 m above mean sea level,
per IEC 947-4
Type of Protection
IP2X in connected state
Finger Protection
safe from touch by fingers and
back of hand per VDE 0106,
Part 100