Rockwell Automation introduces a new category of relays

designed to meet the latest and emerging worldwide safety

standards. These safety control relays offer special features 

to enable you to design safe control circuits with current 

ratings up to 20 Amps.

Bulletin 700S Safety Control Relays provide mechanically-linked 

contacts on all poles. Mechanically-linked contacts are required in

feedback circuits for modern safety applications, such as e-stops,

safety gates, light curtains, and master control relays.

Mechanically-Linked Contacts

This feature allows detection of a welded contact condition.

Mechanically-linked contacts are linked together; they are not

independent. If a N.O. contact welds, all N.C. contacts remain

open. If a N.C. contact welds, all N.O. contacts remain open.

Double-Break Contacts

This design provides better protection against contact welding

than a single break design. It offers greater DC load breaking

capability and better isolation. This feature also provides

separation of N.O. and N.C. circuits. Double-break contacts open

the circuits in two places, creating two air gaps and reducing the

probability of welded contacts by more that 50% compared to 

a single-break design.

Easy Identification

The red faceplate allows easy identification of safety 

devices. This face place displays the IEC 60947-5-1 

mechanically-linked symbol.

Anti-Tamper

The anti-tamper feature ensures the long-term integrity of your

safety system. All contact blocks are permanently fixed to ensure

that the safety function is not jeopardized. Manual operation and

field modifications are prevented.

Product Profile

Safety Control Relays

Designed To Meet Worldwide 
Safety Standards

700S-CF (8 pole)

700S-P (4 –12 pole)

IEC mechanically-linked symbol

Double-break contacts
reduce the probability of a
welded contact.

Summary of Contents for Bulletin 700S-CF

Page 1: ...Safety Control Relays The Safe Solution Bulletin 700S CF Bulletin 700S P...

Page 2: ...Break Contacts This design provides better protection against contact welding than a single break design It offers greater DC load breaking capability and better isolation This feature also provides s...

Page 3: ...ntrol Relaysprovidemechanically linked positivelyguided contacts which are required in feedback circuits for modern safety applications The positively guided N C auxiliary contacts will not change sta...

Page 4: ...CF530 C 700S CF530Z C 4 4 700S CF440 C 700S CF440Z C 3 5 700S CF350 C 700S CF350Z C Voltage 12 24 32 36 42 48 100 100 110 110 120 127 200 200 220 208 208 240 220 230 50 Hz R K V W X Y KP D P S KG F 6...

Page 5: ...17 kW 690V 30 kW 60 C Ith 20 A 6 A 230V 8 kW 400V 14 kW 690V 24 kW DC 12 Control of DC resistive loads IEC 947 EN 60947 24V 12 A 12 A 48V 9 A 9 A 60V 5 0 A 3 5 A 110V 3 5 A 3 5 A 125V 3 0 A 3 0 A 220V...

Page 6: ...old coil W 8 5 Operating Times AC 50 60 Hz Pickup Time ms 15 30 Dropout Time ms 10 60 DC Pickup Time ms 40 70 Dropout Time ms 7 15 With integrated suppression ms 14 20 With diode suppression ms 70 95...

Page 7: ...4 6 1 4 2 4 5 2 3 16 60 2 23 64 35 1 25 64 700S CF Safety Control Relays with mm inches Auxiliary contact block for side mounting 1 or 2 pole a 9 a 23 64 Electronic Timing Module on coil terminal side...

Page 8: ...for use in safety circuits It is designed to reduce the possibility of a welded contact and with external monitoring a welded contact can be detected if one ever occurs It features mechanically linke...

Page 9: ...1 700S P310 700S DCP310Z24 2 2 700S P220 700S DCP220Z24 7 1 700S P710 700S DCP710Z24 6 2 700S P620 700S DCP620Z24 5 3 700S P530 700S DCP530Z24 4 4 700S P440 700S DCP440Z24 3 5 700S P350 700S DCP350Z24...

Page 10: ...t 120V AC 14 million operations at 1A break at 120V AC 6 million operations at 1A break at 24V DC Coil Voltage Range AC 85 110 DC 80 110 Battery Charging 85 115 Coil Consumption 50 Hz 60 Hz AC Inrush...

Page 11: ...pole Bulletin 700S P Relay Approximate Shipping Weight AC 0 79 kg 1 75 lbs DC 1 45 kg 3 20 lbs AC 164 31 6 15 32 7 94 5 16 DC 187 17 7 3 8 89 69 3 17 32 79 38 3 1 8 57 15 2 1 4 Provision for 2 8 10 Mf...

Page 12: ...36 LOAD 3 43 44 43 44 LOAD 4 53 54 53 54 LOAD 5 63 64 63 64 LOAD 6 73 74 73 74 LOAD 7 83 84 83 84 OUTPUTS SAFETY 1 CR 2 CR Interlock CR Industrial Relay 700S P 700S CF Note 1 CR and 2 CR are Allen Br...

Page 13: ...relays 11 23 12 24 11 23 12 24 MOTION BUS L1 L2 L3 K1 K2 BULLETIN 700S SAFETY COROL RELAY K1 K2 N C MECHANICALLY LINKED CONTACT E STOP LATCHING E STOP BUTTON START MOMENTARY PUSH BUTTON GUARD CLOSED...

Page 14: ...fe Provides greater user flexibility for the number of N O and N C contacts Use 3 700S CF relays and this diagram to construct the circuit Numbers shown are the line numbers where the contacts for thi...

Page 15: ...3Y 700 Z Included in Factory Wired Units 700 ZP LOAD 2 LOAD 3 LOAD 4 LOAD 5 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 B1X B1Y B1X B1Y B1Y B1X B2X B3X B4X B2Y B3Y B4Y B2Y B2Y B2X B2X B3Y B3Y B3X...

Page 16: ...eadquarters for Allen Bradley Products Rockwell Software Products and Global Manufacturing Solutions Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 200...

Reviews: