Parameters & Programming
22
F Group – Basic Function Parameters
A Group – Advanced Function Parameters
Parameter
Number
Parameter Name / Description
Min./Max
Range
Units
Factory
Defaults
Basic Functions
U
1
K
1
F01
[Frequency Command]
When parameter
A
01- [Frequency Command Select]
is set to 00 or 01, this parameter will display the
commanded frequency. When
P
A01 - [Frequency
Command Select] is set to 02, this parameter can
be used to change the commanded frequency on
the fly and write the value into parameter
A
20 -
[Internal Frequency]. When a preset frequency is
active, this parameter can be used to program or
change the value of the preset input on the fly while
writing the value into the corresponding parameter
(
P
A21 - [Preset Frequency 1] –
P
A35 - [Preset
Frequency 15]).
Note: The value Is changed in real time and written to memory
without using the Enter key.
This parameter
can be changed while motor is running.
0.0/360.0
0.1 Hz
N/A
N/A
F02
[Accel Time 1]
Time for the drive to ramp from 0.0 Hz to
P
A04 -
[Maximum Frequency]
This parameter
can be changed while motor is running.
0.1/3000
<1000, 0.1 s
>1000, 1 s
10.0
10.0
F03
[Decel Time 1]
Time for the drive to ramp from
P
A04 - [Maximum
Frequency] to 0.0 Hz
This parameter
can be changed while motor is running.
0.1/3000
<1000, 0.1 s
>1000, 1 s
10.0
10.0
F04
[Start Key Direction]
Sets the direction of motor rotation when the drive
is set to Start Key mode, which is controlled by
P
A02 - [Start Command Select] and digital input
setting 31 {OPE}.
Settings:
00=Forward
01=Reverse
02=Control Terminal – Digital inputs
(C01-C05) settings 00 {FW} and 01 {RV}
determine direction of Start Key.
00/02
Numeric Value
00
0.0
Parameter
Number
Parameter Name / Description
Min./Max
Range
Units
Factory
Defaults
Basic Functions
U
1
K
1
A01
[Frequency Command Select]
Selects the source of the frequency command for
the drive.
Note: If any preset frequency inputs are active, all
other frequency commands will be ignored.
Settings:
00= Keypad frequency potentiometer
01=Input O/OI (Analog reference)
02=Internal frequency (
P
F01 -
[Frequency Command]/
P
A20 -
[Internal Frequency])
00/02
Numeric Value
01
01
A02
[Start Command Select]
Selects the source of the start command. Settings:
01=Control terminal block
02=Start Key (Input from Start Key on drive keypad)
Note:
If
P
C03 is set to 21, terminals P24 and 3 must be jumpered for drive to run.
01/02
Numeric Value
01
01
1