ArmorBlock MaXum 8 Input / 8 Output Module
5
Publication 1792D-5.20 - October 1998
Connect the Input / Output Cord Sets to the MaXum Module
This module uses 5 pin micro (12mm) style PCB mounted connectors.
Eight micro caps cover the connectors on your module. Remove the caps
and connect your cord sets to the appropriate ports. This product has two
inputs or outputs per I/O connector. Use a “Y” splitter cable for access to
all I/O connections. For more information on these cables, see the Product
Data publication 1792-2.1
Use the micro caps to cover and seal unused ports. Pinout diagrams for the
connectors are shown next.
!
ATTENTION:
• Make sure all connectors and caps are securely tightened
to properly seal the connections against leaks and
maintain IP67 requirements.
• For maximum noise immunity, input and output cable
return wires must be properly terminated. When inputs
and outputs are connected in loopback, return wires
should be connected together.
• I/O cable length should be less than 30 meters.
Input Micro-Connector
(View into Socket)
Pin 1 Sensor Source voltage
Pin 2 Input B
Pin 3 Return Logic Ground
1
Pin 4 Input A
Pin 5 Not Used
Output Micro-Connector
(View into Socket)
Pin 1 Not Used
Pin 2 Output B
Pin 3 Auxiliary Power Ground
Pin 4 Output A
Pin 5 Not Used
41452
1
Logic Ground is approximately 0.4V above DeviceNet V- measured at the module.
1
5
3
4
2
1
5
3
4
2
AB Parts