ArmorBlock-LP 16 Input Module
8
Publication 1792-5.6 – September 1997
Network Status Indicator NS
Indication
Status
Flashing Green
On-line, not connected
Solid Green
Link OK, on-line connected
Flashing Red
At least 1 I/O connection is in the timed-out state
Solid Red
Incorrect baud rate, or a duplicate Mac ID exists
Module Status Indicator MS
Indication
Status
OFF
No power, or no network access
Flashing Green/OFF
On-line but not connected
Solid Green
On-line, link okay, connected
Flashing Red
Recoverable fault
Solid Red
Critical failure
Sensor Short Circuit Indicator OVL
Indication
Status
OFF
Sensor source voltage operating correctly
Solid Red
1 or more Sensor source voltage shorts
Input I/O Status Indicators A and B
Indication
Status
OFF
No valid input signal present
Yellow
Valid input signal present
Module and Sensor Power Supply Status Indicators U
S
and U
L
Indication
Status
OFF
Power supply is not functioning correctly
Green
Power Supply is operating