Allen-Bradley ArmorBlock-LP 1792-IB16LP Installation Instructions Manual Download Page 3

3

 ArmorBlock-LP 16 Input Module

Publication 1792-5.6 – September 1997

Set up a system (as shown below) to communicate with your
ArmorBlock module to set the node address and communication rate to
meet your system requirements.

30194–M

Host computer with 

DeviceNetManager

software

Power from 9V dc power supply adapter

1770-KFD

RS-232 module

Power Supply

Open style connector

to sealed mini–connector

Mount the ArmorBlock Module

Mount the block module directly to the machine or device. Complete
mounting dimensions are shown below.

Mounting Dimensions

2.0

(51)

1.1

(27)

1.1

(27)

1.1

(27)

1.25

(32)

1.0

(25.5)

1.3

(33)

1.5

(39)

2.4

(60)

1.4

(36)

6.0

(152)

4.2

(107)

0.18

(4.5)

1.8

(45)

1.5

(38)

30198–M

Use 3 #8 (4mm) screws to mount block

Inches

(Millimeters)

1

2

34

5

6

7

8

A

B

A

B

A

B

A

B

A

B

A

B

A

B

A

B

Summary of Contents for ArmorBlock-LP 1792-IB16LP

Page 1: ...as no switches to set You set module parameters using the DeviceNet Manager Software cat no 1787 MGR or similar configuration tool Contents This box contains 1 ArmorBlock LP module Package containing 10 write on indicator tabs and 7 micro caps 1 DeviceNet right hand aluminum T port tap part number 97042401 Installation Instructions European Union Directive Compliance If this product is installed w...

Page 2: ...770 4 1 Automation Systems Catalog publication B111 Install Your ArmorBlock Module Installation of the ArmorBlock module consists of setting the node address and communication rate in the ArmorBlock module mounting the ArmorBlock module connecting the wiring communicating with your module Set the Node Address Each ArmorBlock comes with its internal program set for node address 63 and a communicati...

Page 3: ...rom 9V dc power supply adapter 1770 KFD RS 232 module Power Supply Open style connector to sealed mini connector Mount the ArmorBlock Module Mount the block module directly to the machine or device Complete mounting dimensions are shown below Mounting Dimensions 2 0 51 1 1 27 1 1 27 1 1 27 1 25 32 1 0 25 5 1 3 33 1 5 39 2 4 60 1 4 36 6 0 152 4 2 107 0 18 4 5 1 8 45 1 5 38 30198 M Use 3 8 4mm screw...

Page 4: ... plugs to cover and seal unused ports Pinout diagrams for these connectors are shown below ATTENTION Make sure all connectors are securely tightened to properly seal the connections against leaks and maintain IP67 requirements Connecting the Input Wiring Connect input wiring to the micro connectors which screw into mating connectors on the front of the block Make connections as shown below 1 2 3 4...

Page 5: ...nnection Consumes Produces Polled 0 Bytes 3 Bytes Bit Strobe 0 Bytes 3 Bytes Change of State 0 Bytes 3 Bytes Polled device a master initiates communication by sending its polled I O message to the ArmorBlock module The 16 input module scans the inputs and fault bit producing a response that reflects their status Change of state productions occur when an input changes or an input source voltage fau...

Page 6: ...ces 3 IS Reserved Where I Input IS Sensor source voltage fault Word Bit Description Produces 1 00 07 Input bits bit 00 corresponds to input 1A bit 01 to input 2A and so on 0 input off 1 the input is on Produces 2 00 07 Input bits bit 00 corresponds to input 1B bit 01 to input 2B and so on 0 input off 1 the input is on Produces 3 00 06 Reserved 3 07 Sensor source voltage fault bit this bit is set 1...

Page 7: ... Network Status Indicator OVL Sensor Short Circuit Indicator US Sensor Power Supply Status Indicator UL Module Power Supply Status Indicator A and B Input I O Status Indicators MS Module Status Indicator A B A B A B A B A B A B A B A B 1 2 3 4 5 6 7 8 Note This module contains a circuit to protect the DeviceNet power supply from short circuits in an attached sensor or sensor cable If you connect a...

Page 8: ...twork access Flashing Green OFF On line but not connected Solid Green On line link okay connected Flashing Red Recoverable fault Solid Red Critical failure Sensor Short Circuit Indicator OVL Indication Status OFF Sensor source voltage operating correctly Solid Red 1 or more Sensor source voltage shorts Input I O Status Indicators A and B Indication Status OFF No valid input signal present Yellow V...

Page 9: ...dule Indicators Network Status red green Module Status red green Sensor Power Supply Status green Module Power Supply Status green Short Circuit Sensors red I O Status yellow Communication Rate in Baud 125k 250k 500k selectable General Specifications DeviceNet Power Voltage Current 11 0 25 0V dc 100mA no powered sensors 900mA full sensor load Dimensions Inches Millimeters 6 0H X 2 4W X 2 0D 152H X...

Page 10: ...Bulgaria Canada Chile China PRC Colombia Costa Rica Croatia Cyprus Czech Republic Denmark Ecuador Egypt El Salvador Finland France Germany Greece Guatemala Honduras Hong Kong Hungary Iceland India Indonesia Ireland Israel Italy Jamaica Japan Jordan Korea Kuwait Lebanon Malaysia Mexico Netherlands New Zealand Norway Pakistan Peru Philippines Poland Portugal Puerto Rico Qatar Romania Russia CIS Saud...

Reviews: