Rockwell Automation Publication 857-UM003B-EN-P - December 2017
5
857-VPA3CG Profibus DP Option Module
Data Response Message from the 857 Relay
The response is eight bytes long consisting of three fields.
The Identifier word, ID, contained in the Data Request Message, consists of 3
fields with a bit configuration is shown below.
Error codes in value field in case of response type 0111.
Request and Response Messages Examples
The master requests the measured active power from the device. The hexadecimal
byte values are:
The slave responds with the active power value.
The hexadecimal byte values are:
ID
(1)
(1) Type and number of the requested data.
IND
(2)
(2) Requested index.
VALUE
(3)
(3) Value of the requested data or error code.
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Response Type
(1)
(1) 0001
Read (0010 = Write).
0111
Request Rejected.
SM
(2)
(2) 0
Spontaneous bit (not used).
Parameter Number
(3)
(3) 0…2047
The number of the requested parameter.
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
0
Illegal parameter
18
Other fault
101
Unknown request type
ID
(1)
(1) 1
Request type is read.
0 00
Parameter number of active power P is 0.
IND
(2)
(2) 00 00
Index is 0.
VALUE
(3)
(3) 00 00 00 00
Dummy value.
10
00
00
00
00
00
00
00
ID
(1)
(1) 1
Response type is “Value is ready”.
000
Parameter number is 0. (Copy of request message parameter number).
IND
(2)
(2) 00 00
Index is 0 (Copy of request message index).
VALUE
(3)
(3) 00 00 OD 7A
The active power is 3450 kW (ID7A
16
= 3450
10
).
10
00
00
00
00
00
0D
7A