857-VPA3CG Profibus DP Option Module

PROFIBUS-DP

Optimized for high speed and inexpensive hook-up, this PROFIBUS version is 
designed especially for communication between automation control systems and 
distributed I/O at the device level. 

PROFIBUS-DP can be used to replace parallel signal transmission with 24V or 
0...20 mA.

PROFIBUS-PA

PROFIBUS-PA is designed especially for process automation. It permits sensors 
and actuators to be connected to one common bus line even in intrinsically safe 
areas. PROFIBUS-PA permits data communication and power over the bus using 
2-wire technology according to the international standard IEC 1158-2.

PROFIBUS-FMS

PROFIBUS-FMS is the general-purpose solution for communication tasks at the 
cell level. Powerful FMS services open up a wide range of applications and 
provide great flexibility. PROFIBUS-FMS can also be used for extensive and 
complex communication tasks.

PROFIBUS specifies the technical and functional characteristics of a serial 
fieldbus system with which decentralized digital controllers can be networked 
together from the field level to the cell level. PROFIBUS distinguishes between 
master devices and slave devices.

Master devices determine the data communication on the bus. A master can send 
messages without an external request when it holds the bus access rights (the 
token). Masters are also called active stations in the PROFIBUS protocol.

Slave devices are peripheral devices. Typical slave devices include input/output 
devices, valves, drives, and measuring transmitters. They do not have bus access 
rights and they can only acknowledge received messages or send messages to the 
master when requested to do so. Slaves are also called passive stations.

PROFIBUS-DP Device Profiles

This section outlines the different PROFIBUS-DP device profiles. 

Continuous Mode with Fixed Data Set

In this mode, the 857 protection relay is sending a configured set of parameters 
continuously to the PROFIBUS-DP master.

Calculation of the PROFIBUS-DP Buffer Length

The needed buffer length for PROFIBUS-DP data transfer depends on the 
biggest offset of any activated parameter and the size of this parameter. The offset 
and the activation for each available parameter are configurable.

Summary of Contents for 857-VPA3CG

Page 1: ...ations in manufacturing process and building automation Vendor independence and openness are guaranteed by the PROFIBUS standard EN 50170 With PROFIBUS devices of different manufactures can communicat...

Page 2: ...rial fieldbus system with which decentralized digital controllers can be networked together from the field level to the cell level PROFIBUS distinguishes between master devices and slave devices Maste...

Page 3: ...ted PROFIBUS DP data items in InBuf The size of Eimp item is 4 bytes The parameter Direct05C Direct Operate Object 5 Close has the biggest offset 13 of all activated PROFIBUS data items in OutBuf The...

Page 4: ...uf 8byte Select the corresponding module INPUT OUTPUT 8 Byte from the gsd file for example VPA_00F7 gsd when configuring the PROFIBUS DP master for this device Data Request Message from the PROFIBUS M...

Page 5: ...ested data IND 2 2 Requested index VALUE 3 3 Value of the requested data or error code Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Response Type 1 1 0001 Read 0010 Write 0111 Request Rejec...

Page 6: ...nd Other Parameters The PROFIBUS parameters can be changed from the relay front panel or by SetPointPS program VX 007 Cable X5 Relay back panel Remote port VPA 3 CG Attached to 35 mm DIN RAIL PROFIBUS...

Page 7: ...ware_Release HW1 0 Software_Release SW1 0 9 6_supp 1 baud rate supported 19 2_supp 1 baud rate supported 93 75_supp 1 baud rate supported 187 5_supp 1 baud rate supported 500_supp 1 baud rate supporte...

Page 8: ...data telegram without data in state CLEAR not accepted Slave_Family 0 Max_Diag_Data_Len 16 Unit_Diag_Bit 0 OK Unit_Diag_Bit 1 ERROR 1 Unit_Diag_Bit 2 ERROR 2 Unit_Diag_Bit 3 ERROR 3 Unit_Diag_Bit 4 ER...

Page 9: ...7 9 857 VPA3CG Profibus DP Option Module EndModule Module INPUT 16 Byte 0x57 EndModule Module INPUT 32 Byte 0x5F EndModule Module INPUT 64 Byte 0x40 0x5F EndModule Module INPUT 128 Byte 0x40 0x7F EndM...

Page 10: ...length is increased by the use of repeaters The use of more than three repeaters in series is not recommended Table 2 PROFIBUS DP Connections Interface 9 pin DSUB connector female Transfer method RS...

Page 11: ...rmination Table 6 Recommended Cables Belden PROFIBUS data cable 3079 A Olflex PROFIBUS cable 21702xx Siemens SINEC L2 LAN cable for PROFIBUS 6XVI 830 0AHIO Station 1 Station 2 RxD TxD P 3 DGND 5 VP 6...

Page 12: ...5V 6 VP Supply voltage of the terminating resistant P 7 NC Not connected 8 RxD TxD N Receive data transmission data negative 9 NC Not connected Resource Description 857 Protection System for Feeder an...

Page 13: ......

Page 14: ...des Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer http www rockwellautomation com global support direct dial page Literature Libra...

Reviews: