839E Solid-State Flow Sensors User Manual
Pub #10000004735 Ver 03, May 2012
15
Basic settings
Function
group
Function
(display)
Description
BASE
(basic
functions)
Display assignment:
OFF
Display of current measured value or of configured
switch point (switch 1)
Display of current measured value or of configured
switch point (switch 1) rotated 180°
Display of current medium temperature
Display of current medium temperature rotated 180°
Factory setting: current measured valued in %
Display medium temperature unit °C or °F
Factory setting: °C
NOTE: Only visible if the current medium
temperature is selected in the DISP mode.
Measured value damping with regard to display
value and output:
0 (no damping) or 9…40 sec. (in increments of 1
second)
Factory setting: 0 sec.
Behavior as per DESINA: The PIN of the M12
connector is assigned in accordance with the
guidelines of DESINA.
(DESINA = DistributEd and Standardized INstAllation
technology for machine tools and manufacturing
systems)
CAL
(Calibration)
Setting for maximum flow rate occurring.
100% value
Setting for minimum flow rate occurring.
0% value