839E Solid-State Flow Sensors User Manual
12
Pub #10000004735 Ver 03, May 2012
Navigating the “Learn” function
Figure 10 Navigating the “Learn” function using the Calibration (CAL) function group as an
example
➊
Select the HIF (Learn High Flow) or LOWF (Learn Low Flow) function with the E key
➋
Select the “RUN” function with the + key, learn function is initialized
➌
Select the “WAIT” function with the + key, press for longer than 2 sec.
➍
Accept (“learn”) the current measured value after approx. 10 sec. - “OK” appears on the
display
➎
If “NOK” (not OK) appears on the display after 60 sec., no current measured value was set
➏
Return to the CAL function group (Home position) with the E key
Notes!
1. Programming buttons [E], [-], and [+] may need to be pressed and held for several
seconds before displaying the expected response.
2. When performing a calibration the 839E may require up to 60 seconds to learn the high
or low flow rate. The display will indicate “WAIT” during the learn process.
3. After configuring the 839E to the desired settings, press and hold the [E] key until
“SAVE” appears; press the [+] or [-] key until “YES” appears. Press and hold the [E] key
until “SAVE” appears. Depending on the configuration changes the display may
indicate a number or a blinking “INIT.” Wait for the blinking “INIT” to change to another
value. This indicates the 839E is ready for operation.
Summary of Contents for 839E
Page 1: ...Solid State Flow Sensors USER MANUAL 839E...
Page 29: ...839E Solid State Flow Sensors User Manual Pub 10000004735 Ver 03 May 2012 27...
Page 30: ...839E Solid State Flow Sensors User Manual 28 Pub 10000004735 Ver 03 May 2012...
Page 31: ...839E Solid State Flow Sensors User Manual Pub 10000004735 Ver 03 May 2012 29...
Page 32: ...Publication 10000004735 Ver 03 May 2012 2012 Rockwell Automation Printed in the U S A...