2
Rockwell Automation Publication 836P-IN002B-EN-P - December 2017
Non-display Solid-state Pressure Transmitter
Specifications (Continued)
Measuring Ranges
Gauge Pressure
bar
Measuring Range
0…1
0…1.3
0…2
0…2.5
0…4
0…6
0…9
0…13
0…17
0…20
Overpressure Limit
2
2.6
4
5
8
12
18
26
34
40
Measuring Range
0…24
0…34
0…68
0…99
0…137
0…206
0…344
0…399
0…551
0…689
Overpressure Limit
48
68
136
198
274
412
688
798
1,102
1,378
psi
Measuring Range
0…14.5
0…20
0…30
0…36.2
0…60
0…100
0…145
0…200
0…250
0…300
Overpressure Limit
29
40
60
72
120
200
290
400
500
600
Measuring Range
0…362
0…500
0…1,000
0…1,450
0…2,000
0…3,000
0…5,000
0…5,800
0…8,000
0…10,000
Overpressure Limit
724
1,000
2,000
2,900
4,000
6,000
10,000
10,600
16,000
20,000
Absolute Pressure
bar
Measuring Range
0…1
0…1.3
0…2
0…2.5
0…4
0…6
0…9
0…13
0…17
0…20
Overpressure Limit
2
2.6
4
5
8
12
18
26
34
40
psi
Measuring Range
0…14.5
0…20
0…30
0…36.2
0…60
0…100
0…145
0…200
0…250
0…300
Overpressure Limit
29
40
60
72
120
200
290
400
500
600
Vacuum and +/- Measuring Range
bar
Measuring Range
-1…1
-1…1.3
-1…2
-1…2.5
-1…4
-1…6
-1…9
-1…13
0…17
0…20
Overpressure Limit
2
2.6
4
5
8
12
18
26
34
40
psi
Measuring Range
-30 in
Hg…14.5
-30 in
Hg…20
-30 in
Hg…30
-30 in
Hg…36.2
-30 in
Hg…60
-30 in
Hg…100
-30 in
Hg…145
-30 in Hg…
200
-30 in
Hg…250
-30 in
Hg…300
Overpressure Limit
29
40
60
72
120
200
290
400
500
600
Performance Characteristics
Reference Operation Conditions (per IEC 61298-1)
Operating Conditions: Environment
Load
Analog signal 4…20 mA:
(Power supply -8V)/0.02 A
Temperature
15…25 °C (59…77 °F)
Ambient temperature range
1/4 in. NPT:
-
30…+100 °C (-22…+212 °F)
G 1/4 in.:
-
30…+100 °C (-22…+212 °F)
G 1/2 in.:
-
30…+100 °C (-22…+212 °F)
SAE 7/16-20 UNF:
-
20…+100 °C (-4…+212 °F)
Atmospheric pressure
860…1060 mbar
Settling time
< 4 ms
Humidity
45…75 % r. h.
Medium temperature
Switch on time
< 15 ms
Mounting position
As required
Accuracy Data
Power supply
24V DC
Storage temperature
-40…+70 °C (-40…+158 °F)
mBar models: non-
repeatability measuring range
≤ 0.1 bar ≤ 0.2% span
≤ 0.1% of span
mBar models range of measure ≤ 0.1 bar: ≤ 0.2% of span
≤ 0.1 bar: ≤ 0.1% of span
Vacuum resistance
10 mbar
abs
(0.145 psi)
Signal noise
≤ ± 0.3% of span
Humidity
45…75 % r. h.
Temperature error at 0…80 °C
(32…176 °F) in rate
temperature range
Typical: 1.0% of span
Maximum: 2.5% of span
Service life
10 million load cycles
Shock resistance
500 g (17.64 oz)
(IEC 60068-2-27, mechanical)
Long term drift
≤ ± 0.1% of span
Short circuit resistance
vs. Analog -
Range of measure
≤ 0.1 bar: ≤ ± -0.5% of span
≤ 0.4 bar: ≤ ± -0.2% of span
> 0.4 bar: ≤ ± -0.1% of span
Reverse polarity protection vs. Analog -
Non-linearity
≤ ± 0.5% of span
Vibration resistance
10 g (0.35 oz)
(IEC 60068-2-6, under resonance)
Ingress protection (per
IEC
60529)
IP67 – M12x1 4 pin