Rockwell Automation Publication 825-UM004D-EN-P - November 2012
179
ASCII Serial Communications
Chapter
12
TARGET R (Level 2)
The
TARGET R
command resets the front-panel tripping targets and releases
the trip signal if the fault condition has vanished and lockout conditions are not
present. If you issue the
TARGET R
command at the relay serial port or use the
front-panel Test/Reset push button and the relay tripping targets do not reset,
verify that the fault condition and all lockouts have cleared.
TIME (Level 1 or 2)
The
TIME
command displays the relay clock (24 hours). To set the clock, type
TIME hh:mm:ss
and then press Enter.
Separate the hours, minutes, and seconds with colons, semicolons, spaces,
commas, or slashes. For example, set 22:47:36 by typing
TIME 22:47:36
and
then pressing Enter:
View or Change Settings with
Front Panel Serial Port
View Settings
Use the
SHOW
command to view relay settings. The
SHOW
command is
available from Access Level 1 and Access Level 2.
Table 108 lists the
SHOW
command options.
You can append a setting name to each of the commands to specify the first
setting to display (e.g.,
SHO 50P1P
displays the relay settings starting with
setting 50P1P). The default is the first setting.
The
SHOW
command displays only the enabled settings. To display all the
settings, including disabled/hidden settings, append an
A
to the
SHOW
command (e.g.,
SHOW A
).
Table 108 - SHOW Command Options
Command
Description
SHOW
Show relay settings.
SHO A
Show all relay settings: enabled, disabled/hidden.
SHO P
Show front serial port settings.
SHO M
Show I/O mapping settings.
Summary of Contents for 825-P
Page 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Page 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Page 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Page 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Page 265: ......