Industrial Integrated Display Computers
Rockwell Automation Publication 6181P-IN010D-EN-P - April 2012
Install the Computer
The computers support the following mounting options:
•
Panel mount
•
Wall mount (for non-display computers)
Panel Mounting Guidelines
Observe these guidelines when installing the unit in a panel:
•
Remove all electrical power from the panel before making the cutout.
•
Confirm that there is adequate space behind the panel. For specific information refer to
Mounting Clearances
on
page 8
.
•
Cut supporting panels to specifications before installation. Take precautions so metal
cuttings do not enter components already installed in panel.
Supporting panels must be at least 14 gauge to ensure proper sealing against water and
dust and to provide proper support. The mounting hardware supplied accommodates
panel thickness between 1.5 to 5.5. mm (0.06…0.25 in.).
•
Make sure the area around the panel cutout is clear.
Panel Cutout Dimensions
The products must be appropriately mounted in the panel cutout dimensions specified below.
Included with the shipped product is 6181P and 6181X Industrial Computers Cutout Template,
publication
6181P-DS002
, with a cutout template for each display computer model.
ATTENTION:
Failure to follow these guidelines may result in personal injury or damage to the
panel components.
Computer Model
Cutout Dimensions (H x W), approx
1200P
254.0 x 324.0 mm (10.0 x 12.76 in.)
1500P
285.0 x 386.6 mm (11.24 x 15.22 in.)
1700P
329.5 x 424.0 mm (12.97 x 16.69 in.)