268
Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Appendix B
Module Tag Definitions
5069-IB8S and 5069-IB8SK
Module Tags
This section describes the tags that are associated with the 5069-IB8S or
5069-IB8SK module.
Input Tags
describes the 5069-IB8S or 5069-IB8SK module input tags.
5069-OBV8S
SIL2 CPU
5069-L3100ERMS2
Compact GuardLogix
5069-OBV8S
5069-IB8S
5069-IB8S
OUTPUT
OUTPUT
SA P
ow
er
MOD P
ow
er
Safety Modules
Table 89 - 5069-IB8S or 5069-IB8SK Module Input Tags
Name
Data Type
Definition
Valid Values
RunMode
BOOL
Module’s operating state
• 0 = Idle
• 1 = Run
ConnectionFaulted
BOOL
Indicates if a connection is running.
The module sets this tag to 0 when connected. If the
module is not connected, it changes the tag to 1.
• 0 = Connection running
• 1 = Connection not running
DiagnosticActive
BOOL
Indicates if any diagnostics are active or if the prognostics
threshold is reached.
• 0 = No diagnostics active
• 1 = One or more diagnostics are active or the
prognostics threshold is reached
DiagnosticSequenceCount
SINT
Increments for each time a distinct diagnostic condition is
detected, and when a distinct diagnostic condition
transitions from detected to not detected.
Set to zero by product reset or power cycle. Wraps from
255 (-1) to 1 skipping zero.
• 1…255
The value of 0 is skipped except during module
power-up.
Ptxx.Data
BOOL
Indicates the current safety input value.
• 0 = Off
• 1 = On
Ptxx.Fault
BOOL
Indicates one of the following:
• The channel data is inaccurate and
cannot be trusted
for use in the application.
For more information, see
• The channel is set to Not Used.
• 0 = Good data
• 1 = Bad data (faulted) or set to Not Used
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT
: Once the condition that causes
the tag to change to 1 is removed, you must
complete the steps described in
to reset this tag
to 0.
If the tag is 1 because the channel is set to Not
Used, no action is required.
Ptxx.Uncertain
BOOL
Indicates that the channel data can be inaccurate but the
degree of inaccuracy is not known
.
For more information, see
• 0 = Good data
• 1 = Uncertain data
This tag is set to 1 when the module has
reached a critical operating temperature or is
higher the acceptable operating temperature.
IMPORTANT
: Once the condition that causes
the tag to change to 1 is removed, the tag
automatically resets to 0.
Ptxx.ShortCircuit
BOOL
Indicates a short circuit.
• 0 = No short circuit
• 1 = Short circuit
Ptxx.Status
BOOL
Indicates the status of the channel.
• 0 = Bad, causing a fault
• 1 = Good
Testxx.Readback
BOOL
Indicates that a 24V DC power source is present at the
test output.
• 0 = 24V DC power is not present
• 1 = 24V DC power is present