![Allen-Bradley 2711-B6C series Installation Instructions Manual Download Page 10](http://html1.mh-extra.com/html/allen-bradley/2711-b6c-series/2711-b6c-series_installation-instructions-manual_2900783010.webp)
10
PanelView 600 Terminals
41061-004-01(D)
5. Install the 4 mounting clips (2 on top, 2 on bottom); the ends of the clips slide
into the slots on the terminal. Tighten the clip mounting screws by hand until
the gasket seal contacts the mounting surface uniformly.
6. Alternately tighten the mounting clip screws to a torque of 10 inch-pounds.
Do not over–tighten.
7. Remove the 2 protective labels covering the top vents of the terminal.
!
ATTENTION
Tighten mounting clips to a torque of 10 inch-pounds to
provide a proper seal and to prevent potential damage to the
terminal. Allen-Bradley assumes no responsibility for
water or chemical damage to the terminal or other
equipment within the enclosure because of improper
installation.
!
ATTENTION
Remove the protective installation labels covering the top
vents to prevent overheating and damage to the terminal.
Protective Installation Labels
Install 4 Mounting Clips:
Top
- Left and Right Slots
Bottom
- Left and Right Slots