FLEX I/O Power Supply Modules
7
Publication 1794-IN069E-EN-P - September 2018
Install Your Power Supply Module
1.
Hook the lip on the rear of the power supply module onto the top of the DIN
rail, and rotate the power supply module onto the rail.
2.
Press the power supply module down onto the DIN rail until flush. Locking
tab C will snap into position and lock the power supply module to the DIN rail.
3.
If the power supply module does not lock in place, use a screwdriver or similar
device to move the locking tab down while pressing the power supply module
flush onto the DIN rail, and release the locking tab to lock the power supply
module in place. If necessary, push up on the locking tab to lock.
4.
Connect the power supply wiring as shown in
Connect Wiring for your Power
Supply Module
below.
Note:
For panel/Wall mounting, refer to publication
1794-TD013
, Panel Mounting Kit,
catalog number 1794-NM1.
ATTENTION:
During mounting of all devices, be sure that all debris (metal
chips, wire strands, etc.) is kept from falling into the module. Debris that falls
into the module could cause damage on power up.
B
C
A
C
1794-PS13 shown