Allen-Bradley 1794-PS13 Installation Instructions Manual Download Page 3

FLEX I/O Power Supply Modules     

3

Publication 1794-IN069E-EN-P - September 2018

Environment and Enclosure

Preventing Electrostatic Discharge     

This equipment is intended for use in a Pollution Degree 2 industrial 
environment, in overvoltage Category II applications (as defined in IEC 60664-1), 
at altitudes up to 2000 m (6562 ft) without derating.

This equipment is not intended for use in residential environments and may not 
provide adequate protection to radio communication services in such 
environments.

This equipment is supplied as open-type equipment. It must be mounted within 
an enclosure that is suitably designed for those specific environmental 
conditions that will be present and appropriately designed to prevent personal 
injury resulting from accessibility to live parts. The enclosure must have suitable 
flame-retardant properties to prevent or minimize the spread of flame, 
complying with a flame spread rating of 5VA or be approved for the application 
if nonmetallic. The interior of the enclosure must be accessible only by the use 
of a tool. Subsequent sections of this publication may contain additional 
information regarding specific enclosure type ratings that are required to 
comply with certain product safety certifications.

In addition to this publication, see the following:

Industrial Automation Wiring and Grounding Guidelines, publication 

1770-4.1

, for additional installation requirements.

NEMA Standard 250 and IEC 60529, as applicable, for explanations of the 
degrees of protection provided by enclosures.

ATTENTION: 

This equipment is sensitive to electrostatic discharge, which can 

cause internal damage and affect normal operation. Follow these guidelines 
when you handle this equipment:

Touch a grounded object to discharge potential static.

Wear an approved grounding wriststrap.

Do not touch connectors or pins on component boards.

Do not touch circuit components inside the equipment.

Use a static-safe workstation, if available.

Store the equipment in appropriate static-safe packaging when not in use.

Summary of Contents for 1794-PS13

Page 1: ...nformation 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 3 North American Hazardous Location Approval 5 Install Your Power Supply Module 7 Connect Wiring for your Power Supply Modul...

Page 2: ...this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibilit...

Page 3: ...ad rating of 5VA or be approved for the application if nonmetallic The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additi...

Page 4: ...protection provided by the equipment may be impaired Read this document and the documents listed in the Additional Resources section about installation configuration and operation of this equipment be...

Page 5: ...a is known to be nonhazardous Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this eq...

Page 6: ...ystem with the 1794 PS13 power supply The 1794 PS3 power supply provides sufficient 24V DC power to operate 10 adapter modules You can use this 1794 PS3 power supply to operate an entire FLEX I O syst...

Page 7: ...ewdriver or similar device to move the locking tab down while pressing the power supply module flush onto the DIN rail and release the locking tab to lock the power supply module in place If necessary...

Page 8: ...120 230V AC power to the left side terminals on the connectors on the left side of the power supply module as follows 2 Connect terminal G 24V DC to the 24V DC terminal on the first adapter 3 Connect...

Page 9: ...r Modules ATTENTION The total length of wire for terminals H I J and G must not exceed 3m 9 8ft Exceeding the 3m 9 8ft length can reduce noise immunity ATTENTION Input and output wiring must be in acc...

Page 10: ...he power supply Output voltage exceeded 35V DC and overvoltage protection shut the unit down Output current is above 1 4A 1794 PS13 or above 3 2A 1794 PS3 Power 24V DC POWER SUPPLY 1794 PS13 24V COM P...

Page 11: ...r ports North American temp code T3 Terminal screw torque 0 8 Nm 7 lbs in Input 1794 PS13 and 1794 PS3 Attribute 1794 PS13 1794 PS3 Nominal supply voltage 120V AC 50 60 Hz 0 6 A max 230V AC 50 60 Hz 0...

Page 12: ...IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 0 C Ta 55 C 32 F Ta 131 F Temperature surrounding air max 55 C 131 F Temperature nonoperating IEC 60068 2 1 Tes...

Page 13: ...ous Locations certified for U S and Canada See UL File E334470 UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 CE European Union 2014 30 EU EMC Directive complia...

Page 14: ...3 0 10 20 30 40 50 55 60 Max Output Current A Ambient Temperature oC The area within the curve represents the safe operating range for the module under various conditions of user supplied 24V DC suppl...

Page 15: ...69D 35 1 4 A 59 2 3 A Mounting hole dimensions for optional mounting kit B B DIN rail 50 2 0 28 1 2 C C Secure DIN rail approximately every 200 mm Power 24V DC POWER SUPPLY 1794 PS13 24V COM Inches M...

Page 16: ...returned follow these procedures Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form...

Reviews: