5–33
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Publication 17946.5.2 - May 1996
FLEX I/O analog modules are supported by the DeviceNet adapter.
At present, these consist of:
Module Description
Catalog Number:
For image table mapping refer to:
8 Input Analog Module
1794IE8/B
page
5-3
4 Output Analog Module
1794OE4/B
page
4 in/2 out Analog Combo Module 1794IE4XOE2/B
page
8 Input Analog Module (Cat. No. 1794IE8 Series B) Image Table
Mapping
Module Image
I/O Image
Input Data Channel 0
Input Data Channel 1
Input Data Channel 2
Input Data Channel 3
Input Data Channel 4
Input Data Channel 5
Input Data Channel 6
Input Data Channel 7
Underrange
Configure select
Not used
Not used
Not used
Not used
Not used
Input Size
Output Size
0 or 1 Word
1 to 9 Words
PU
Analog Input Module (1794-IE8/B) Read
Decimal Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Size
Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read Words
S
Analog Value Channel 0
Read Word 1
S
Analog Value Channel 1
Read Word 2
S
Analog Value Channel 2
Read Word 3
S
Analog Value Channel 3
Read Word 4
S
Analog Value Channel 4
Read Word 5
S
Analog Value Channel 5
Read Word 6
S
Analog Value Channel 6
Read Word 7
Mapping Data into the
Image Table