Rockwell Automation Publication 1794-IN082D-EN-P - January 2019
FLEX I/O EtherNet/IP Adapters
WARNING:
• This equipment is not resistant to sunlight or other sources of UV radiation.
• This equipment shall be mounted in an ATEX Zone 2 certified enclosure with a
minimum ingress protection rating of at least IP54 (in accordance with EN
60079-15) and used in an environment of not more than Pollution Degree 2
(as defined in EN 60664-1) when applied in Zone 2 environments. The
enclosure must be accessible only by the use of a tool.
• This equipment shall be used within its specified ratings defined by
Rockwell Automation.
• Provision shall be made to prevent the rated voltage from being exceeded by
transient disturbances of more than 140% of the peak rated voltage when
applied in Zone 2 environments.
• The instructions in the user manual shall be observed.
• This equipment must be used only with ATEX certified Rockwell Automation®
backplanes.
• Secure any external connections that mate to this equipment by using screws,
sliding latches, threaded connectors, or other means provided with this product.
• Do not disconnect equipment unless power has been removed or the area is
known to be nonhazardous.
• Enclosure must be marked with the following: "Warning - Do not open when
energized." After installation of equipment into the enclosure, access to
termination compartments shall be dimensioned so that conductors can be
readily connected.
• Earthing is accomplished through mounting of modules on rail.
• Devices shall be used in an environment of not more than Pollution Degree 2.