3
ArmorBlock 16 Input Module
Publication 1792-5.3 – October 1996
Install Your ArmorBlock Module
Installation of the ArmorBlock module consists of:
•
setting the node address in the ArmorBlock module
•
mounting the ArmorBlock module
•
connecting the wiring
•
communicating with your module
•
configuring the parameters
Set the Node Address
Each ArmorBlock comes with its internal program set for node address
63. To set the node address, you need the following:
•
host computer with DeviceNet Manager Software (or similar
configuration software tool)
•
1770-KFD RS-232 module (or similar interface)
•
suitable cables to connect the 1770-KFD to your module and to
connect the 1770-KFD to your host computer
Set the node address to meet your system requirements as follows:
1. Set up a system (as shown below) to communicate with your
ArmorBlock module.
Power from 9V DC Power-Supply Adapter
power supply
open style connector to
sealed mini-female cable
RS-232 module
host computer with the
DeviceNet Manager software
1770-KFD