27
ArmorBlock 16 Input Module
Publication 1792-5.3 – October 1996
Reset Faults using Explicit Message Program Control
You can also reset inputs using the Explicit Message Program Control
feature on the Scanner module master. Refer to the specific scanner
publications for information on using this feature.
The format for the reset explicit message transaction block must
contain 6 words as shown below:
Word
Input Fault
Transaction Header
Word 0
TXID – CMD/STATUS
Word 1
PORT – SIZE
Word 2
Service = 32 hex – MAC ID
Transaction Body
Word 3
Class = 1D hex
Word 4
Instance = 1
Word 5
Attribute = 0
Attribute Data = 0