Environmental Specifications
Attribute
Value
Operating
temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F)
Non-operating
temperature
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…90% noncondensing
Operating altitude
2000 m
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Operating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
10 g
Non-operating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Emissions
CISPR 11:
Group 1, Class A
ESD immunity
IEC 61000-4-2:
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
EFT/B immunity
IEC 61000-4-4:
1 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on signal ports
Surge transient
immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
Conducted RF
immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz