Allen-Bradley 1771-IB Installation Data Download Page 4

DC (12-24V) Input Module

Cat. No. 1771-IB

Installation Data

 4

Figure 1

Connection Diagram (2-Wire Devices)

Input 0

Input 1

Input 2

Input 3

Input 4

Input 5

Input 6

Input 7

DC Common

Not used

DC

Power Supply

+

-

(See Applicable Codes and Laws)

A

0

1

2

3

4

5

6

7

B

(Actual wiring runs in this direction.)

11833-I

Connect one terminal of your 2 or 3–wire input device to terminals 0
through 7 (Figure 1). Connect 3–wire input devices, such as Allen–Bradley
proximity switches (Bulletin 871) to operate in a current source mode
(

Figure 2

).

Connect terminal B to the dc common. Terminal A is not used. Connect the
+dc line to the other terminal of your input devices. Use stranded 14 or 16
gauge wire to minimize the voltage drop over long cable distances.

Important:   You can directly drive terminals on an DC (12–24V) Input
Module (cat. no. 1771–IB) from terminals on the following modules:

DC (10–60V) Output module (cat. no. 1771–OBD)

DC (12–24V) Output module (cat. no. 1771–OB)

Important:    Use the same dc power source to power both modules to
ensure that ground is at the same potential.

Summary of Contents for 1771-IB

Page 1: ...kage current of your 3 wire devices should not exceed 3mA This module contains input filtering to limit the effect of voltage transients caused by contact bounce and or radiated electrical noise The delay due to input filtering is nominally 12 7ms for turning inputs on and 20 7ms for turning inputs off Your module receives its power through the 1771 I O chassis backplane from the chassis power sup...

Page 2: ...ee work station When not in use keep the module in a static shielded bag In this section we tell you how to key your I O chassis install your module and make your wiring connections Keying Your I O Chassis Use the plastic keying bands shipped with each I O chassis to key the I O slots to accept only this type of module The module circuit board is slotted in two places on the rear edge The position...

Page 3: ... the slot that guide the module into position 3 Do not force the module into its backplane connector Apply firm even pressure on the module to seat it properly 4 Snap the chassis latch over the top of the module to secure its position 5 Connect the wiring arm to the module 6 Make wiring connections to the field wiring arm as indicated in Figures 1 and 2 Connecting Wiring to the Input Module Connec...

Page 4: ...as Allen Bradley proximity switches Bulletin 871 to operate in a current source mode Figure 2 Connect terminal B to the dc common Terminal A is not used Connect the dc line to the other terminal of your input devices Use stranded 14 or 16 gauge wire to minimize the voltage drop over long cable distances Important You can directly drive terminals on an DC 12 24V Input Module cat no 1771 IB from ter...

Page 5: ...ction 11834 I The front panel of your module contains 8 red status LED indicators figure 3 The red status indicators are provided for system logic side indication of individual inputs When a red LED lights voltage is present on the terminal The module transfers this information to the backplane for the processor to read Figure 3 Status Indicators Not used Input 0 Input 1 Input 2 Input 3 Input 4 In...

Page 6: ...PE MIDDLE EAST AFRICA HEADQUARTERS Allen Bradley Europe B V Amsterdamseweg 15 1422 AC Uithoorn The Netherlands Tel 31 2975 43500 Telex 844 18042 FAX 31 2975 60222 ASIA PACIFIC HEADQUARTERS Allen Bradley Hong Kong Limited Room 1006 Block B Sea View Estate 28 Watson Road Hong Kong Tel 852 887 4788 Telex 780 64347 FAX 852 510 9436 CANADA HEADQUARTERS Allen Bradley Canada Limited 135 Dundas Street Cam...