
64
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Appendix B
1769 DeviceNet Modules Status Indicators and Data Structures
Output Data Image
The output data image is transferred from the controller to the scanner module.
The following table shows the bit descriptions for the module’s command array.
CompactLogix Status Structure
The second area of the CompactLogix controller input image is the Status
Structure. The status structure consists of these data elements.
Word
Description
Data Type
0 and 1
Module Command Array
2-word array
2…181
Output Data Image
180-word array
Word
Bit
Operating Mode
0
0
1 = Run, 0 = Idle
1
1 = Fault
2
1 = Disable Network
3
Reserved
(1)
(1)
Do not
manipulate reserved bits. Doing so may interfere with future compatibility.
4
1 = Reset
5…15
Reserved
1
0…15
Reserved
Description
Data Type
I.Status.Scan Counter
2 words
I.Status.Device Failure Register
64-bit array
I.Status.Autoverify Failure Register
64-bit array
I.Status.Device Idle Register
64-bit array
I.Status.Active Node Register
64-bit array
I.Status.Status Display
8 bytes
I.Status.Scanner Address
1 byte
I.Status.Scanner Status
1 byte
I.Status.Scrolling Device Address
1 byte
I.Status.Scrolling Device Status
1 byte
I.Status.Device Status
64 bytes
Summary of Contents for 1769-SDN
Page 1: ...Installation Instructions DeviceNet Modules Catalog Numbers 1756 DNB 1769 ADN 1769 SDN...
Page 4: ...4 Rockwell Automation Publication DNET IN001B EN P January 2012 Summary of Changes Notes...
Page 8: ...8 Rockwell Automation Publication DNET IN001B EN P January 2012 Preface Notes...
Page 65: ......
Page 66: ......
Page 67: ......