Attach an end-cap terminator (5) to the last module in the system by
using the tongue-and-groove slots as before.
8.
Lock the end-cap bus terminator (6).
Mount Expansion I/O
Minimum Space
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc.
Allow 50 mm (2 in) of space on all sides for adequate ventilation.
IMPORTANT
You must use a 1769-ECR or -ECL right- or left-end cap to
terminate the end of the serial communication bus.
ATTENTION
During panel or DIN rail mounting of all devices, be sure that all
debris (metal chips, wire strands, etc.) is kept from falling into
the module. Debris that falls into the module could cause
damage on power up.
IMPORTANT
When mounting the CompactLogix system, either use screws
to panel mount the system
OR
use DIN rail. Do
NOT
use
both. Use of both mounting methods may cause hardware
damage and cause the system to fail.