Summary of Contents for 1762-IQ8OW6

Page 1: ...an Hazardous Location Approval 4 Module Description 5 Install the DC Input Relay Output Combination Module 6 Mount the Module on a DIN Rail 6 Mount the Module on a Panel 7 Wire the DC Input Relay Output Combination Module 8 Ground the DC Input Relay Output Combination Module 9 Wire the Finger safe Terminal Block 9 System Assembly 10 Input Memory Map 11 Output Memory Map 12 Specifications 13 Additi...

Page 2: ...tion Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibite...

Page 3: ...nternational Electrotechnical Commission IEC designations ATTENTION Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins Follow these guidelines when you handle the module Touch a grounded object to discharge static potential Wear an approved wrist strap grounding device Do not touch the bus connector or connector pins Do not touch circuit compon...

Page 4: ...nt sujettes à inspection par les autorités locales qualifiées au moment de l installation WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using ...

Page 5: ...em Description 1a upper panel mounting tab 5 bus connector cover 1b lower panel mounting tab 6 flat ribbon cable with bus connector female pins 2 I O diagnostic LEDs 7 terminal block 3 module door with terminal identification label 8 DIN rail latch 4 bus connector with male pins 9 pull loop 1a 7 6 1b 4 5 3 9 1a 6 8 1b 2 ...

Page 6: ...mentarily open and lock into place Use DIN rail end anchors Allen Bradley part number 1492 EA35 or 1492 EAH35 for vibration or shock environments ATTENTION Do not remove protective debris strip until after the module and all other equipment near the module is mounted and wiring is complete Once wiring is complete and the module is free of debris carefully remove protective debris strip Failure to ...

Page 7: ... a good ground contact Mounting screws are required on every module TIP For environments with greater vibration and shock concerns use the panel mounting method described below instead of DIN rail mounting End Anchor End Anchor MicroLogix 1200 Controller MicroLogix 1200 Expansion I O MicroLogix 1200 Expansion I O MicroLogix 1200 Expansion I O 90 3 54 100 3 94 40 4 1 59 40 4 1 59 14 5 0 57 For more...

Page 8: ...field power supply are sinking field devices Field devices connected to the positive side V of the field supply are sourcing field devices 2 Surge Suppression Connecting surge suppressors across your external inductive load will extend the life of the relay contacts For additional details refer to Industrial Automation Wiring and Grounding Guidelines Allen Bradley publication 1770 4 1 ATTENTION Be...

Page 9: ...ial Automation Wiring and Grounding Guidelines Allen Bradley publication 1770 4 1 for additional information Wire the Finger safe Terminal Block When wiring the terminal block keep the finger safe cover in place 1 Route the wire under the terminal pressure plate You can use the stripped end of the wire or a spade lug The terminals will accept a 6 35 mm 0 25 in spade lug 2 Tighten the terminal scre...

Page 10: ...ed to remove the finger safe cover insert a screw driver into one of the square wiring holes and gently pry the cover off If you wire the terminal block with the finger safe cover removed you will not be able to put it back on the terminal block because the wires will be in the way Wire Type Wire Size Terminal Screw Torque Solid Cu 90 C 194 F 0 325 2 080 mm2 22 14 AWG 0 90 Nm 8 lb in Stranded Cu 9...

Page 11: ...r expansion I O begins with slot 1 ATTENTION EXPLOSION HAZARD In Class I Division 2 applications the bus connector must be fully seated and the bus connector cover must be snapped in place In Class I Division 2 applications all modules must be mounted in direct contact with each other as shown on page 6 If DIN rail mounting is used an end stop must be installed ahead of the controller and after th...

Page 12: ...e only w user can write but outputs not available 0 always at 0 or OFF state The output addressing scheme for 1762 expansion I O is shown below 1 I O located on the controller embedded I O is slot 0 I O added to the controller expansion I O begins with slot 1 Word Bit Position 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 0 0 0 0 0 0 0 0 w w w w w w w w O0 x 0 0 Output Data File Slot Number 1 Word Alway...

Page 13: ...ts are driven by a current sourcing field device Field devices connected to the negative side DC Common of the field power supply are sinking field devices Field devices connected to the positive side V of the field supply are sourcing field devices Operating Voltage Range 10 30V DC 30 C 86 F 10 26 4V DC 65 C 149 F Number of Inputs 8 On state Voltage Min 10V DC Off state Voltage Max 5V DC On state...

Page 14: ...tinuous Amps per Point Max Amperes 1 1 Surge Suppression Connecting surge suppressors across your external inductive load will extend the life of the relay contacts For additional details refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Voltamperes Make Break Make Break 240V AC 2 5 A 7 5 A 0 75 A 1800VA 180VA 120V AC 15 A 1 5 A 125V DC 1 0 A 0 22 A 2 2 For DC vol...

Page 15: ... Operation 1 5 g Shock Operating 30 g panel mounted 3 pulses per axis Relay Operation 7 g Non Operating 50 g panel mounted 3 pulses per axis 40 g DIN Rail mounted Vender ID Code 1 Product Type Code 7 Product Code 98 Hazardous Environment Class Class I Division 2 Hazardous Location Groups A B C D ISA ANSI 12 12 01 C UL under CSA C22 2 No 213 Radiated and Conducted Emissions EN50081 2 Class A ESD Im...

Page 16: ... us UL Listed Industrial Control Equipment certified for US and Canada UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers...

Page 17: ...nstalling wiring and operating a MicroLogix 1200 programmable controller system MicroLogix 1200 Programmable Controllers Installation Instructions publication 1762 IN006 Installation guide for the MicroLogix 1200 programmable controller MicroLogix 1100 Programmable Controllers User Manual publication 1763 UM001 A more detailed description of how to install and use your MicroLogix 1100 programmable...

Page 18: ...18 DC Input Relay Output Combination Module Publication 1762 IN018B EN P July 2013 Notes ...

Page 19: ...DC Input Relay Output Combination Module 19 Publication 1762 IN018B EN P July 2013 Notes ...

Page 20: ...perational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature United S...