Allen-Bradley 1756-PA30XT Original Instructions Manual Download Page 4

4

Rockwell Automation Publication 1756-IN619E-EN-P - September 2019

ControlLogix Power Supply

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous 
locations.

Informations sur l'utilisation de cet équipement en environnements dangereux.

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, 
Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on 
the rating nameplate indicating the hazardous location temperature code. When combining 
products within a system, the most adverse temperature code (lowest "T" number) may be used to 
help determine the overall temperature code of the system. Combinations of equipment in your 
system are subject to investigation by the local Authority Having Jurisdiction at the time of 
installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en 
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque 
produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de 
température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans 
un système, le code de température le plus défavorable (code de température le plus faible) peut 
être utilisé pour déterminer le code de température global du système. Les combinaisons 
d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au 
moment de l'installation.

WARNING: EXPLOSION HAZARD

• Do not disconnect equipment unless power has been removed or the area 

is known to be nonhazardous. 

• Do not disconnect connections to this equipment unless power has been 

removed or the area is known to be nonhazardous. Secure any external 
connections that mate to this equipment by using screws, sliding latches, 
threaded connectors, or other means provided with this product.

• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must be changed only in an area 

known to be nonhazardous.

AVERTISSMENT: RISQUE D'EXPLOSION

• Couper le courant ou s'assurer que l'environnement est classé non 

dangereux avant de débrancher l'équipement.

• Couper le courant ou s'assurer que l'environnement est classé non 

dangereux avant de débrancher les connecteurs. Fixer tous les 
connecteurs externes reliés à cet équipement à l'aide de vis, loquets 
coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

• La substitution de composants peut rendre cet équipement inadapté à 

une utilisation en environnement de Classe I, Division 2.

• S'assurer que l'environnement est classé non dangereux avant de changer 

les piles.

European Hazardous Location Approval

The following applies to products marked 

, II 3:

• Such modules are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in 

Annex II to Directive 94/9/EC. See the EC Declaration of Conformity at 

rok.auto/certifications

 for details. The type of protection for 1756-PB50, 1756-PB72, 1756-PB75, 1756-PBXT, and 1756-PB30XT 

is “Ex nA IIC T4 Gc” according to EN 60079-15.

• Such modules may have catalog numbers followed by a “K” to indicate a conformal coating option.
• Such modules are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. 

Such locations correspond to Zone 2 classification according to ATEX directive 1999/92/EC.

• The 1756-PB50, 1756-PB72, 1756-PB75, 1756-PBXT, and 1756-PB30XT comply to Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference ATEX certificate number 

DEMKO13ATEX1325026X.

Summary of Contents for 1756-PA30XT

Page 1: ...he power supply that you can use This table lists the chassis that can be installed with each power supply Topic Page Summary of Changes 5 Tools Required 6 Install the Power Supply 6 Connect the Power...

Page 2: ...ti nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio...

Page 3: ...plicable for explanations of the degrees of protection provided by different types of enclosures Prevent Electrostatic Discharge ATTENTION Thisequipmentissensitivetoelectrostaticdischarge whichcancaus...

Page 4: ...ctions that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product Substitution of components may impair suitability for Class I Division...

Page 5: ...1325026X IECEx UL 14 0008X 1756 PC75 None 1756 PH75 1756 PH75K None 1756 PAXT None 1756 PBXT Ex nA IICT4 Gc DEMKO13ATEX1325026X IECEx UL 14 0008X 1756 PA30XT None 1756 PB30XT Ex nA IICT4 Gc DEMKO13ATE...

Page 6: ...flush with the front of the chassis 4 Tighten the top and bottom screws to fasten the power supply to the chassis 3 18 mm 0 125 in slotted screwdriver Crimper 6 35 mm 0 25 in slotted or 2 Phillips scr...

Page 7: ...ing ATTENTION Do not wire more than one conductor on any single terminal Use 15 A time delay type fuse in all ungrounded power connections IMPORTANT The voltage input connections of the power supplies...

Page 8: ...groove at the front of the power supply 2 Feed a cable tie through the retainer on the v groove 3 To secure the power cable tighten the cable tie 4 Trim any excess cable tie length as appropriate Rem...

Page 9: ...e power 3 Loosen the screws that secure the power supply to the chassis See step 4 on page 6 for the location of the screws on the power supply 4 Slide the power supply out so that the rear connector...

Page 10: ...ure type rating None open style Torque 0 565 N m 5 lb in Dimensions HxWxD approx 14 0 x 11 2 x 14 5 cm 5 51 x 4 41 x 5 71 in Wire size 2 5 mm2 14 AWG solid or stranded copper wire rated at 90 C 194 F...

Page 11: ...13 F Ta 158 F Temperature surrounding air max 70 C 158 F Enclosure type rating None open style Torque 0 565 N m 5 lb in Dimensions HxWxD approx 14 0 x 11 2 x 14 5 cm 5 51 x 4 41 x 5 71 in 14 0 x 7 8 x...

Page 12: ...ion needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ e...