Attribute

1756-PAXT

1756-PBXT

1756-PA30XT

1756-PB30XT

Voltage and current ratings 

Input

120/240V AC, 50/60 Hz, 82VA, 
64 W

18…32V DC, 70 W

120/240V AC, 50/60 Hz, 50 W 
(60VA), 70 °C (158 °F)

24V DC, 50W 70 °C (158 °F)

Output (current capacity)

1.75 A, 24V DC, 
8.0 A, 5.1V DC, 
4.0 A, 3.3V DC, 
1.5 A, 1.2V DC, 
42 W max, 
20 A inrush max

2.1 A, 24V DC, 
10.0 A, 5.1V DC, 
4.0 A, 3.3V DC, 
1.5 A, 1.2V DC, 
52 W max, 
30 A inrush max

1.25 A, 24V DC; 
6.0 A, 5.1V DC; 
2.0 A, 3.3V DC; 
1.5 A, 1.2V DC; 
30 W max, 
20 A inrush max

1.25 A, 24V DC; 
6.0 A, 5.1V DC; 
2.0 A, 3.3V DC; 
1.5 A, 1.2V DC; 
30 W max, 
20 A inrush max

Isolation voltage

250V (continuous), Reinforced Insulation Type, Power Input to Backplane

Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-25 °C < Ta < +70 °C (-13 °F < Ta < +158 °F)

Temperature, surrounding air, max

70 °C (158 °F)

Enclosure type rating

None (open-style)

Torque

0.565 N•m (5 lb•in)

Dimensions (HxWxD), approx

14.0 x 11.2 x 14.5 cm (5.51 x 4.41 x 5.71 in.)

14.0 x 7.8 x 14.5 cm (5.51 x 3.07 x 5.71 in.)

Wire size

2.5 mm2 (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max

North American temperature code

T4

T4A

T4

ATEX temperature code

-

T4

-

T4

IECEx temperature code

-

T4

-

T4

Resource

Description

1756 ControlLogix Specifications Technical Data, publication 

1756-TD006

Provides technical specifications for ControlLogix chassis.

1756 ControlLogix Power Supplies Specifications Technical Data, publication 

1756-TD005

Provides technical specifications for ControlLogix power supplies.

ControlLogix Chassis Installation Instructions, publicatio

1756-IN621

Provides information on how to install ControlLogix chassis.

ControlLogix System User Manual, publication 

1756-UM001

Provides instructions for installation and use of ControlLogix Systems, application design, and other 
general information for these systems.

Industrial Automation Wiring and Grounding Guidelines, publication

 1770-4.1

 

Provides general guidelines for installing a Rockwell Automation industrial system.

Product Certifications website, 

http://www.rockwellautomation.com/rockwellautomation/certification/overview.page

 

Provides declarations of conformity, certificates, and other certification details.

Summary of Contents for 1756-PA30XT

Page 1: ...he power supply that you can use This table lists the chassis that can be installed with each power supply Topic Page Summary of Changes 5 Tools Required 6 Install the Power Supply 6 Connect the Power...

Page 2: ...ti nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio...

Page 3: ...plicable for explanations of the degrees of protection provided by different types of enclosures Prevent Electrostatic Discharge ATTENTION Thisequipmentissensitivetoelectrostaticdischarge whichcancaus...

Page 4: ...ctions that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product Substitution of components may impair suitability for Class I Division...

Page 5: ...1325026X IECEx UL 14 0008X 1756 PC75 None 1756 PH75 1756 PH75K None 1756 PAXT None 1756 PBXT Ex nA IICT4 Gc DEMKO13ATEX1325026X IECEx UL 14 0008X 1756 PA30XT None 1756 PB30XT Ex nA IICT4 Gc DEMKO13ATE...

Page 6: ...flush with the front of the chassis 4 Tighten the top and bottom screws to fasten the power supply to the chassis 3 18 mm 0 125 in slotted screwdriver Crimper 6 35 mm 0 25 in slotted or 2 Phillips scr...

Page 7: ...ing ATTENTION Do not wire more than one conductor on any single terminal Use 15 A time delay type fuse in all ungrounded power connections IMPORTANT The voltage input connections of the power supplies...

Page 8: ...groove at the front of the power supply 2 Feed a cable tie through the retainer on the v groove 3 To secure the power cable tighten the cable tie 4 Trim any excess cable tie length as appropriate Rem...

Page 9: ...e power 3 Loosen the screws that secure the power supply to the chassis See step 4 on page 6 for the location of the screws on the power supply 4 Slide the power supply out so that the rear connector...

Page 10: ...ure type rating None open style Torque 0 565 N m 5 lb in Dimensions HxWxD approx 14 0 x 11 2 x 14 5 cm 5 51 x 4 41 x 5 71 in Wire size 2 5 mm2 14 AWG solid or stranded copper wire rated at 90 C 194 F...

Page 11: ...13 F Ta 158 F Temperature surrounding air max 70 C 158 F Enclosure type rating None open style Torque 0 565 N m 5 lb in Dimensions HxWxD approx 14 0 x 11 2 x 14 5 cm 5 51 x 4 41 x 5 71 in 14 0 x 7 8 x...

Page 12: ...ion needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ e...

Reviews: