Troubleshoot Your Module
ControlLogix® analog I/O module have status indicators on the front of the
module that are used to monitor module operation.
Status Indicators for the
1756-IF8I Module
Topic
Page
Status Indicators for the 1756-IF8I Module
Status Indicators for the 1756-IRT8I Module
Status Indicators for the 1756-IR12 Module
Status Indicators for the 1756-IT16 Module
Status Indicators for the 1756-OF8I Module
Use Logix Designer Application for Troubleshooting
Troubleshoot Incorrect Readings on the Module
Indicator
Status
Description
OK
Steady green
The module is in a normal operating state in Run mode.
Flashing green
The module passed internal diagnostics and is not actively controlled or
the connection is open and the controller is in Program mode.
Flashing red
Previously established communication has timed out.
Steady red
Replace the module.
ST
Steady yellow
The channel is operating as expected.
Flashing yellow
The channel is being calibrated.
Off
The channel is not in use or is faulted.
FLT
Off
The channel is operating as expected or it is not in use.
Steady red
•
The channel is faulted. Possible causes of the fault include:
–
Underrange/overrange detection
–
Sourcing Over Current
–
CRC from ADC always Bad
–
Wire off detection
For more information on these causes see Chapter 3,
Analog Input Module on page 41
Flashing red
The channel is faulted and is being calibrated. See the previous row for
more information about faults.