166
Rockwell Automation Publication 1756-UM540E-EN-P - December 2017
Chapter 9
Troubleshoot Your Module
Status Indicators for the
1756-IRT8I Module
Status Indicators for the
1756-IR12 Module
Indicator
Status
Description
OK
Steady green
The module is in a normal operating state in Run mode.
Flashing green
The module passed internal diagnostics and is not actively controlled or
the connection is open and the controller is in Program mode.
Flashing red
Previously established communication has timed out.
Steady red
Replace the module.
ST
Steady yellow
The channel is operating as expected.
Flashing yellow
The channel is being calibrated.
Off
The channel is not in use or is faulted.
FLT
Off
The channel is operating as expected or it is not in use.
Steady red
•
The channel is faulted. Some possible causes of the fault include:
–
Underrange/overrange detection
–
Wire off detection
–
CRC from ADC always Bad
For more information on these causes see Chapter 4,
Flashing red
The channel is faulted channel is being calibrated. See the previous row for
more information about faults.
Indicator
Status
Description
OK
Steady green
The module is in a normal operating state in Run mode.
Flashing green
The module passed internal diagnostics and is not actively controlled or
the connection is open and the controller is in Program mode.
Flashing red
Previously established communication has timed out.
Steady red
Replace the module.
ST
Steady yellow
The channel is operating as expected.
Flashing yellow
The channel is being calibrated.
Off
The channel is not in use or is faulted.
FLT
Off
The channel is operating as expected or it is not in use
Steady red
•
The channel is faulted. Some possible causes of the fault include:
–
Underrange/overrange detection
–
Wire off detection
–
CRC from ADC always Bad
For more information on these causes see Chapter 4,
Flashing red
The channel is faulted and is being calibrated. See the previous row for
more information about faults.