Chapter 3 Configurable Flowmeter Module Features and Operational Modes
Fill Mode
Use Fill mode to choose volume or time for Trickle mode operation.
Trigger On
Use Trigger On to determine what state triggers output 0 to energize. For
example, you can configure the module to trigger an output when the prover
reaches a particular frequency.
These events can trigger an output in Filler mode:
•
Frequency - Input exceeds a certain frequency (latched).
•
Acceleration - Input accelerates at a particular rate (latched).
•
Full Flow State - Module is operating in the full flow state.
•
Trickle Flow State - Module is operating in trickle state.
Tie to Counter
Choose which output is connected to which channel’s Totalizer. There are two
outputs on each module.
Fill Enable
Use Fill Enable to reset the Fill Total value. This feature does not reset the Gross
Volume or Net Volume. You must use the reset for the Totalizer to reset those
values.
Fill Start
Fill Start starts the Fill upon transition from 0 to 1. Reset the Fill Enable to reset
this feature. If any outputs are connected to the channel, they will transition
back to reset and close the valve.