Allen-Bradley 1747-ASB Installation Instructions Manual Download Page 4

4

        Remote I/O Adapter Module     

Publication 1747-IN014C-EN-P - January 2003

Hardware Features

Required Tools and Equipment

Have the following tools and equipment ready:

medium blade screwdriver

(2) 1/2 watt terminating resistors (See page 18 for correct size.)

an adequate length of RIO communication cable (Belden™ 9463) for your 
specific application. (See page 18 for maximum cable distances.)

Determining System Power Requirements

Review the power requirements of your system to ensure that the chassis supports 
placement of the 1747-ASB module. The adapter consumes 600 mA at 5V dc. For a 
detailed list of device load currents, refer to the 

SLC 500 Fixed Hardware Style 

Installation and Operation Manual

, publication number 1747-6.21; the 

SLC 500 

Modular Hardware Style User Manual,

 publication number 1747-UM011, or the 

appropriate Technical Data sheet.

U

FOR HAZ. LOC. 

A196

L

SLC 500

CA

T

SER

SERIAL

 NO.

FRN

SA

ADAPTER

1 2

3

7

8

SW1

O

N

1 2

3

7

8

SW2

O

N

1 2

3

5

46

5

46

5

46

78

SW3

O

N

IMPORT

ANT

:

INST

ALL
 IN SLOT

 ZERO OF MODULAR CHASSIS ONL

Y

REMOTE I/O 

ADAPTER 

MODULE

F

AC 1M

MADE IN USA

CURRENT

 REQUIREMENT

: 375mA

LISTED IND. CONT

. EQ.

CLASS 1, GROUPS 

A, B, C 

AND 

D, 
DIV
. 2

OPERA

TING 

TEMPERA

TURE

CODE T3C

1 23

45

6
7
8

SW1

1 2

3
4
5
6
7
8

SW2

1 2

3
456

7
8

SW3

O

N

O

N

LINE 1
SHLD

LINE 2
NC
IN

RET

(MSB)

LOGICAL  
RACK

(LSB)

LOGICAL  
GROUP

BAUD
RA TE

PRI/COMP

RSV

(MSB)

(LSB)

IMAGE
SIZE

HLS

PRL

RESP

LAST CHA

ADDR
MODE

SP MODE

KEY

1747-ASB

ST A TUS

COMM

F AUL T

FAULT LED 
(Red)

COMM LED 
(Green)

Status 
Display

Door 
Label

Cable Tie Slots

Self-Locking Tab

DIP Switches

Manufacturing 
Test Plug

RIO Link and 
Processor 
Restart 
Lockout 
Connector

Summary of Contents for 1747-ASB

Page 1: ...reux 2 1747 ASB Module Overview 3 Required Tools and Equipment 4 Determining System Power Requirements 4 Slot Addressing 5 Configuring the Module 6 Installing the Module 10 Connecting RIO Link Devices...

Page 2: ...N HAZARD Substitution of components may impair suitability for Class I Division 2 Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non ha...

Page 3: ...on chassis It maps the image of the I O modules in its remote chassis and remote expansion chassis directly to the SLC or PLC processor image Output data is sent from the scanner of either the SLC or...

Page 4: ...mber 1747 6 21 the SLC 500 Modular Hardware Style User Manual publication number 1747 UM011 or the appropriate Technical Data sheet U FOR HAZ LOC A196 L SLC 500 CAT SER SERIAL NO FRN SA ADAPTER 1 2 3...

Page 5: ...LC and PLC processors address the I O modules residing in the chassis by logical rack and logical group Slot addressing refers to how each chassis slot is assigned a specific amount of the 1747 ASB mo...

Page 6: ...group 1 Slot Addressing Input Image Output Image One slot is addressed as one logical group 1 2 Slot Addressing Input Image Output Image One slot is addressed as two logical groups Slot Slot Slot Slot...

Page 7: ...r sends Reset Adapter Decide commands to the 1747 ASB module Processor Restart Lockout PRL determines whether the 1747 ASB module automatically resumes RIO link communications if communication is lost...

Page 8: ...ue as octal with SW1 6 as the least significant bit LSB For example SW1 1 SW1 2 SW1 3 SW1 4 SW1 5 SW1 6 Rack ON OFF ON ON ON OFF 21 octal 17 decimal 0 1 0 0 0 1 1 O N 2 4 5 6 7 8 3 SW1 Logical Rack Nu...

Page 9: ...ze Bit 2 ASB Module Image Size Bit 1 ASB Module Image Size Bit 0 Baud Rate SW2 1 SW2 2 Baud Rate ON ON 57 6K default ON OFF 115 2K OFF ON 230 4K OFF OFF INVALID Primary Complementary Chassis ON Primar...

Page 10: ...0 LSB Specialty I O Mode I O Module Keying Hold Last State ON Hold Last State OFF Do not Hold Last State default Processor Restart Lockout after lost communications ON Automatic Restart default OFF Pr...

Page 11: ...located on each self locking tab and slide the module out 4 Cover all unused slots with the Card Slot Filler Catalog Number 1746 N2 Connecting RIO Link Devices Link Wiring The modules are connected i...

Page 12: ...e table on page 18 for baud rate and maximum cable distances Correct Link Wiring Incorrect Link Wiring IMPORTANT No two devices can be connected to the same point on the link An example of correct and...

Page 13: ...ground only at one end of the RIO link Baud Rate Resistor size Using Extended Node Capability All Baud Rates 82 1 2 Watt Not Using Extended Node Capability 57 6K baud 150 1 2 Watt 115 2K baud 150 1 2...

Page 14: ...anner is attempting to communicate with the 1747 ASB module Use a momentary switch Class 1 Division 2 to short terminals IN and RET together The processor restart lockout is removed as soon as the swi...

Page 15: ...s transferred on the network by logical rack and logical group number Refer to Remote I O Scanner User Manual publication number 1747 6 6 for more information on the 1747 SN Using a PLC as a Master If...

Page 16: ...must be used when working with a PLC processor as a master Adhere the octal labels over the existing decimal labels as shown below Contact your local Allen Bradley distributor if you need to order add...

Page 17: ...le and set SW3 8 to the OFF position check mode 4 Replace the 1747 ASB module in slot 0 5 Apply power to your system Checking Operation During normal operation PLC or SLC in Run mode the 1747 ASB modu...

Page 18: ...eak at 5 57 Hz Acceleration 2 5Gs at 57 2000 Hz Shock operating 30Gs Agency Certification when product or packaging is marked UL Listed CSA certified Class I Division 2 Groups A B C D CE compliant for...

Page 19: ...da For Refer to this Document Pub No A more detailed description on how to install and use your Remote I O Adapter Module Remote I O Adapter Module User Manual 1747 6 13 A more detailed description on...

Page 20: ...hardware module within the first 24 hours of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getti...

Reviews: