Remote I/O Adapter Module
Publication 1747-IN014C-EN-P - January 2003
Installing the Module
1.
Make sure system power is off.
ATTENTION
!
Disconnect power before attempting to install or remove the
module.
1
O
N
24
5
6
7
8
3
SW3
Hold Last State
Processor Restart Lockout
Link Response
Last Chassis/PLC-3 Backup
Addressing Mode Bit 1 (MSB)
Addressing Mode Bit 0 (LSB)
Specialty I/O Mode
I/O Module Keying
Hold Last State
ON Hold
Last
State
OFF
Do not Hold Last State (default)
Processor Restart Lockout
(after lost communications)
ON Automatic
Restart
(default)
OFF
Processor Lockout
Last Chassis
ON
Not Last Chassis (default)
OFF
Last Chassis
Specialty I/O Mode
ON Discrete
(default)
OFF
Block Transfer
I/O Module Keying
ON Save
Mode
(default)
OFF
Check Mode
Link Response
ON Restricted
(default)
OFF
Unrestricted
Addressing Mode
ON ON
Invalid
ON
OFF
1-slot Addressing (default)
OFF
ON
1/2-slot Addressing
OFF
OFF
2-slot Addressing