All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM032A-EN-P — April 2014
11
Bulletin 1606 Switched Mode Power Supplies
12. Efficiency and Power Losses
Efficiencies for 3-Phase operation:
3AC 400V
3AC 480V
Efficiency
typ.
95.4%
95.2%
at 48V, 20A
Average efficiency
*)
typ.
94.7%
94.6%
25% at 5A, 25% at 10A, 25% at 15A. 25% at
20A
Power losses
typ.
1.5W
1.5W
with activated shut-down
typ.
9.5W
9.8W
at 48V, 0A (no load)
typ.
24.1W
25.0W
at 48V, 10A (half load)
typ.
46.3W
48.4W
at
48V,
20A
(full
load)
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Efficiencies when using only 2 legs of a 3-phase system:
2AC 400V
2AC 480V
Efficiency
typ.
94.4%
**)
94.7%
**)
at
48V,
20A
Power losses
typ.
56.9W
**)
53.7W
**)
at 48V, 20A (full load)
**) Curves
can
be
found
in
section
25.4.
Fig. 12-1
Efficiency vs. output current at 48V,
typ.
Fig. 12-2
Losses vs. output current at 48V,
typ.
Efficiency
4
6
8
10
12
14
16 18 20A
92
93
94
Output Current
95
96%
3x480Vac
3x400Vac
Power Losses
0
2
4
6
8 10 12 14
20A
10
0
30
40
50
60W
16 18
20
3x400Vac
3x480Vac
Output Current
Fig. 12-3
Efficiency vs. input voltage at 48V,
20A, typ.
Fig. 12-4
Losses vs. input voltage at 48V, 20A,
typ.
Efficiency
350
400
450
500 3x550Vac
94.9
95.0
95.1
95.2
Input Voltage
95.3
95.4
95.5%
Power Losses
350
400
450
500 3x550Vac
44
45
46
47
Input Voltage
48
49
50W