
All parameters are specified at 24V, 40A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
6
Rockwell Automation Publication 1606-RM005A-EN-P - February 2014
Bulletin 1606 Switched Mode Power Supplies
6. Output
Output voltage
nom.
24V
Adjustment range
min.
24-28V
guaranteed
max.
30V
***)
at clockwise end position of potentiometer
Factory setting
typ.
24.1V
±0.2%, at full load, cold unit, in “single use” mode
typ.
24.1V
±0.2%, at full load, cold unit, in “parallel use” mode
typ.
25.1V
at no load, cold unit, in “parallel use” mode
Line regulation
max.
10mV
3x323-576Vac
Load regulation
max.
50mV
in “single use” mode: static value, 0A 40A, see Fig. 6-1
typ.
1000mV
in “parallel use” mode: static value, 0A 40A,
see Fig. 6-2
Ripple and noise voltage
max.
100mVpp
20Hz to 20MHz, 50Ohm
Output current
nom.
40A
continuously available at 24V, see Fig. 6-1 and Fig. 6-2
nom.
34.3A
continuously available at 28V, see Fig. 6-1 and Fig. 6-2
nom.
60A
short term (4s) available BonusPower
*)
, at 24V,
see Fig. 6-1, Fig. 6-2 and Fig. 6-4
nom.
51.5A
short term (4s) available BonusPower
*)
, at 28V,
see Fig. 6-1, Fig. 6-2 and Fig. 6-4
typ.
110A
up to 25ms, output voltage stays above 20V, see Fig.
6-4. This peak current is available once every second.
See section 25.2 for more peak current measurements.
Output power
nom.
960W
continuously available at 24-28V
nom.
1440W
*)
short
term
available
BonusPower
*)
at 24-28V
BonusPower
time
typ.
4s
duration until the output voltage dips, see Fig. 6-3
BonusPower
recovery time
typ.
7s
overload free time to reset power manager, see Fig. 6-5
Overload behavior
cont. current
see Fig. 6-1
Short-circuit current
**)
min.
40A
continuous, load impedance 25mOhm, see Fig. 6-1
max.
44A
continuous,
load
impedance
25mOhm,
see
Fig.
6-1
min.
60A
short-term (4s), load impedance 25mOhm, see Fig. 6-1
max.
68A
short-term (4s), load impedance 25mOhm, see Fig. 6-1
typ.
46A
continuous, load impedance <10mOhm
max.
51A
continuous, load impedance <10mOhm
Output capacitance
typ.
10 200μF
included in the power supply
*)
BonusPower, short term power capability (up to typ. 4s)
The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short-
term duration is hardware-controlled by an output power manager. BonusPower is repeatedly available. Detailed information
can be found in section 25.1. If the power supply is loaded longer with the BonusPower
than shown in the bonus-time diagram (see
Fig. 6-3), the max. output power is automatically reduced to 960W.
**)
Discharge current of output capacitors is not included.
***)
This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. There is no
guarantee that this value can be achieved. The typical value is about 28.5V.