All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM044A-EN-P — March 2014
5
Bulletin 1606 Switched Mode Power Supplies
4. DC-Input
1606-XLS240E, 1606-XLS240EA, 1606-XLS240EC:
DC input
nom.
DC 110-150V
-20%/+25%
DC input range
min.
88-187Vdc
continuous operation
DC input current
typ.
2.37A
110Vdc, at 24V, 10A
1606-XLS240E-D:
DC input
nom.
DC 110-300V
-20%/+25%
DC input range
min.
88-375Vdc
continuous operation
DC input current
typ.
2.37/ 0.85A
110/300Vdc, at 24V, 10A
All units:
Allowed Voltage L/N to Earth
max.
375Vdc
continuous, IEC 62103
Turn-on voltage
typ.
80Vdc
steady state value
Shut-down voltage
typ.
55Vdc
steady state value
Fig. 4-1
Wiring for DC Input
Instructions for DC use:
+
-
Load
L
PE
+
-
Power Supply
AC
Battery
N
DC
a) Use a battery or similar DC source.
For other sources, contact Rockwell Automation.
b) Cpole to L and –pole to N.
c) Connect the PE terminal to a earth wire or to the machine
ground.
d) A supply from the intermediate DC-bus of a frequency
converter is not recommended and can cause a
malfunction or damage the unit.