All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM044A-EN-P — March 2014

25

Bulletin 1606 Switched Mode Power Supplies

23.9. Daisy Chaining of Outputs

 

Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current 
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block as 
shown in Fig. 23-7. 

 

Fig. 23-6   Daisy chaining of outputs 

 

Fig. 23-7   Using distribution terminals 

 

Power

+  +

-  -

Supply

Input

Output

Load

+

-

max 25A!

Power

+  +

-  -

Supply

Input

Output

 

 

Load

+

-

Distribution

Terminals

Power

+  +

-  -

Supply

Input

Output

Power

+  +

-  -

Supply

Input

Output

 

23.10. Series Operation

 

Unit A

AC

DC

Unit B

AC

DC

-

+

-

+

Load

+

-

Earth
(see notes)

Power supplies of the same type can be connected in series for higher 
output voltages. It is possible to connect as many units in series as needed, 
providing the sum of the output voltage does not exceed 150Vdc. Voltages 
with a potential above 60Vdc are no longer SELV and can be dangerous. 
Such voltages must be installed with a protection against touching.  
Earthing of the output is required when the sum of the output voltage is 
above 60Vdc.  
Avoid return voltage (e.g. from a decelerating motor or battery) which is 
applied to the output terminals.  
Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power 
supplies on top of each other. Do not use power supplies in series in mounting orientations other than the standard 
mounting orientation (input terminals on bottom and output terminals on the top of the unit).  
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. 
 

23.11. Inductive and Capacitive Loads

 

The unit is designed to supply any kind of load, including unlimited inductive of capacitive loads.

Summary of Contents for 1606-XLS240E

Page 1: ...Increase Output Power 24 23 8 Parallel Use for Redundancy 24 23 9 Daisy Chaining of Outputs 25 23 10 Series Operation 25 23 11 Inductive and Capacitive Loads 25 23 12 Operation on Two Phases 26 23 13...

Page 2: ...in nearly every environment possible The integrated output power manager a wide range input voltage design and virtually no input inrush current make installation and usage simple Diagnostics are eas...

Page 3: ...fer to section 24 14 This device is designed for convection cooling and does not require an external fan Do not obstruct airflow and do not cover ventilation grid e g cable conduits by more than 30 Ke...

Page 4: ...92 at 24V 10A see Fig 3 4 Crest factor typ 1 65 1 67 1 85 at 24V 10A Start up delay typ 800ms 650ms 340ms see Fig 3 2 Rise time typ 8ms 8ms 8ms 0mF 24V 10A see Fig 3 2 typ 15ms 15ms 15ms 10mF 24V 10A...

Page 5: ...e min 88 375Vdc continuous operation DC input current typ 2 37 0 85A 110 300Vdc at 24V 10A All units Allowed Voltage L N to Earth max 375Vdc continuous IEC 62103 Turn on voltage typ 80Vdc steady state...

Page 6: ...uppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V Inrush current max 10Apeak 10Apeak 10Apeak over entire temperature range typ 5Apeak 4Apeak 7Apeak...

Page 7: ...r load impedance 100mOhm max 15A continuous load impedance 10mOhm see Fig 6 1 Output capacitance typ 7 000 F included inside the power supply BonusPower short term power capability up to typ 4s The po...

Page 8: ...h o r t t e r m Adjustment Range Bonus Time 0 110 120 130 140 150 160 1 2 3 7 4 5 6 8 9 10s min max typ Output Power Fig 6 3 BonusPower recovery time Power Demand 100 t t Limitation by Power Manager O...

Page 9: ...adjusted output voltage level Contact opens As soon as the output voltage dips more than 10 below the adjusted output voltage Short dips will be extended to a signal length of 250ms Dips shorter than...

Page 10: ...loaded with 25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with 100 of the nominal load for the rest...

Page 11: ...by the lifetime expectancy of the built in electrolytic capacitors Lifetime expectancy is specified in operational hours and is calculated according to the capacitor s manufacturer specification The...

Page 12: ...5 6mm2 0 5 6mm2 0 5 6mm2 Stranded wire 0 5 4mm2 0 5 4mm2 0 5 4mm2 American Wire Gauge 20 10 AWG 20 10 AWG 20 10 AWG Wire stripping length 10mm 0 4inch 10mm 0 4inch 10mm 0 4inch Screwdriver not applica...

Page 13: ...DC OK relay contact is synchronized with the DC OK LED See section 8 for details D Output voltage potentiometer Open the flap to adjust the output voltage Factory set 24 1V E DC OK LED green On when...

Page 14: ...40 of 200Vac 70 of 200Vac 0Vac 20ms 40Vac 200ms 70Vac 500ms 0Vac 20ms 80Vac 200ms 140Vac 500ms Criterion A Criterion C Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000 4...

Page 15: ...al 2 17 8Hz 1 6mm 17 8 500Hz 2g 2 hours axis IEC 60068 2 6 Shock 30g 6ms 20g 11ms 3 bumps direction 18 bumps in total IEC 60068 2 27 Altitude 0 to 2000m 0 to 6 560ft without any restrictions 2000 to 6...

Page 16: ...current typ 0 19mA 0 44mA 100Vac 50Hz TN TT mains IT mains typ 0 29mA 0 65mA 120Vac 60Hz TN TT mains IT mains typ 0 53mA 1 04mA 230Vac 50Hz TN TT mains IT mains 0 25mA 0 54mA 110Vac 50Hz TN TT mains...

Page 17: ...60950 1 RECOGNIZED UNDER FILE NUMBER E244404 for use in the U S A UL 60950 1 and Canada C22 2 No 60950 Information Technology Equipment Level 3 ISA 12 12 01 CSA C22 2 No 213 CSA Certified inder File...

Page 18: ...free of halogens wires and cables are not PVC insulated The production material within our production does not include following toxic chemicals Polychlorized Biphenyl PCB Polychlorized Terphenyl PCT...

Page 19: ...s run in time unless noted otherwise Rockwell Automation Publication 1606 RM044A EN P March 2014 19 Bulletin 1606 Switched Mode Power Supplies 22 Accessories 22 1 1606 XLB Wall Mounting Bracket This b...

Page 20: ...ffer Unit s Power Supply Load AC The buffer unit does not require any control wiring It can be added in parallel to the load circuit at any given point Buffer units can be added in parallel to increas...

Page 21: ...spond with a thermal shut down after a period of time Use the maximum duty cycle curve Fig 23 2 to check if the average output current is below the nominal current Fig 23 1 Repetitive pulse loads defi...

Page 22: ...current for 5ms typ 10ms DIV Output Voltage Output Current 24V 0A 20A 20 5V Output Voltage 24V Output Current 0A 1ms DIV 50A 14V Peak load 20A resistive for 50ms Output voltage dips from 24V to 20 5V...

Page 23: ...rotect wires and circuits If the ampere value and the characteristics of the MCB are adapted to the wire size that is used the wiring is considered as thermally safe regardless of whether the MCB open...

Page 24: ...r system availability Redundant systems require a certain amount of extra power to support the load in case one power supply unit fails The simplest way is to put two power supplies in parallel This i...

Page 25: ...s for higher output voltages It is possible to connect as many units in series as needed providing the sum of the output voltage does not exceed 150Vdc Voltages with a potential above 60Vdc are no lon...

Page 26: ...r circuit breakers are specified in section 23 4 External Input Protection 23 13 Use in a Tightly Sealed Enclosure When the power supply is installed in a tightly sealed enclosure the temperature insi...

Page 27: ...current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 23 8 Mounting Orientation A Standard orientation Power Supply OUTPUT Output Current 0 10 20...

Page 28: ...getting your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing fa...

Reviews: