Allen-Bradley 1606-XLPRED Reference Manual Download Page 9

All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM035A-EN-P — April 2014

9

Bulletin 1606 Switched Mode Power Supplies

9. EMC 

The redundancy module is suitable for applications in industrial environment as well as in residential, commercial and 
light industry environment without any restrictions. A detailed EMC report is available upon request. 

 

EMC Immunity 

According generic standards: EN 61000-6-1 and EN 61000-6-2 

Electrostatic discharge  

EN 61000-4-2 

Contact discharge 
Air discharge 

8kV 
15kV 

Criterion A 
Criterion A 

Electromagnetic RF field 

EN 61000-4-3 

80MHz-2.7GHz 

10V/m 

Criterion A 

Fast transients (Burst) 

EN 61000-4-4 

Input lines 
Output lines 

2kV 
2kV 

Criterion A 
Criterion A 

Surge voltage on input lines  EN 61000-4-5 

 - 

200V 

Criterion A 

Surge voltage on output line  EN 61000-4-5 

 - 

200V 

Criterion A 

Conducted disturbance 

EN 61000-4-6 

0.15-80MHz 

10V 

Criterion A 

Power-frequency magnetic 
field *) 

EN 61000-4-8 

50Hz 

30A/m 

Criterion A 

Criteria:

 

A:

    Redundancy module shows normal operation behavior within the defined limits. 

Notes:

 

*)

    A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields, e.g. hall  

elements, electrodynamic microphones, etc. 

 

 

EMC Emission 

According generic standards: EN 61000-6-3 and EN 61000-6-4 

Conducted emission  

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 

Class B, input lines *) 

 

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 

Class B, output lines *) 

Radiated emission 

EN 55011, EN 55022 

Class B 

This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 

*) 

Provided, that power sources connected on the inputs fulfill the class B requirements as well. 

 

Allen-Bradley HMIs

Summary of Contents for 1606-XLPRED

Page 1: ...is full 13 7V or flat 10V 24Vdc A figure with the unit Vdc at the end is a momentary figure without any additional tolerances included may A key word indicating flexibility of choice with no implied p...

Page 2: ...ccup overload behavior Unique quick connect spring clamp terminals allow for a safe and fast installation and a large international approval package for a variety of applications makes this unit suita...

Page 3: ...oes not require an external fan Do not obstruct airflow and do not cover ventilation grid e g cable conduits by more than 30 Keep the following installation clearances 40mm on top 20mm on the bottom 5...

Page 4: ...m 10 16A for 5 seconds max 16A at continuous overload or short circuit see note 2 Reverse current max 0 6mA per input 40 C to 60 C Reverse voltage max 200Vdc voltage applied to the output continuously...

Page 5: ...U2 U1 Voltage Drop U1 UOUT Output A V IOUT UOUT Variable Load 0 10A 1606 XLPRED Input 1 Input 2 Output Fig 3 3 Input to output voltage drop when only one input draws current Voltage Drop U1 UOUT Not u...

Page 6: ...lectrolytic capacitors Therefore the lifetime expectancy is extremely high Input output current conditions Input 2x5A Output 10A Lifetime expectancy min 25 years at 24V and 40 C min 25 years at 24V an...

Page 7: ...iameter 2 8mm including ferrule Wire stripping length 6mm 0 25inch Pull out force 10AWG 80N 12AWG 60N 14AWG 50N 16AWG 40N according to UL486E Terminals shipped in open position Fig 6 1 Connecting a wi...

Page 8: ...otherwise 8 Rockwell Automation Publication 1606 RM035A EN P April 2014 Bulletin 1606 Switched Mode Power Supplies 7 Functional Diagram Fig 7 1 Functional diagram Input 1 Input 2 Output 8 Front Side a...

Page 9: ...e on output line EN 61000 4 5 200V Criterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Power frequency magnetic field EN 61000 4 8 50Hz 30A m Criterion A Criteria A Redundancy mo...

Page 10: ...e Fig 10 2 Altitude de rating 0 7A 1000m or 5 C 1000m 2000m 6500ft see Fig 10 2 Over voltage category not applicable The concept of the overvoltage category is used for equipment energized directly fr...

Page 11: ...IEC 60529 Penetration protection 2 5mm e g screws small parts Over temperature protection not included Input transient protection not included Output transient protection not included Internal input f...

Page 12: ...IZED E168663 for use in the U S A UL 60950 1 and Canada C22 2 No 60950 Information Technology Equipment Level 3 CSA 22 2 No107 1 01 60950 1 CSA Certified under File Number 240020 II 3G Ex nA IIC T4 Gc...

Page 13: ...0g 0 31lb DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The DIN rail height must be added to the unit depth 91mm to calculate the total required installati...

Page 14: ...ses or mains circuits if possible Set the power supply in Parallel Use mode if this feature is available It is desirable to set the output voltages of all power supplies to the same value 16 2 Inducti...

Page 15: ...D IN 1 Output IN 2 Alarm Monitor Load XLP50E Power Supply L N Input Output DC OK XLP50E Power Supply L N Output Input DC OK XLPRED IN 1 Output IN 2 I I I Note Whenever possible use separate mains syst...

Page 16: ...Standard orientation Redundancy Module INPUT OUTPUT Output Current 0 10 20 30 40 60 C 2 6 8 10A 50 4 Ambient Temperature Fig 16 5 Mounting Orientation B Upside down Redundancy Module INPUT OUTPUT Out...

Page 17: ...Allen Bradley HMIs...

Page 18: ...ial help in getting your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manuf...

Reviews: