All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM035A-EN-P — April 2014
7
Bulletin 1606 Switched Mode Power Supplies
6. Terminals and Wiring
Input and output
Type
Bi-stable, quick-connect spring clamp terminals.
IP20 Finger safe construction.
Suitable for field- and factory installation.
Solid wire
0.3-4mm
2
Stranded wire
0.3-2.5mm
2
American Wire Gauge
26-12 AWG
Max. wire diameter
2.8mm (including ferrule)
Wire stripping length
6mm / 0.25inch
Pull-out force
10AWG:80N, 12AWG:60N, 14AWG:50N,
16AWG:40N (according to UL486E)
Terminals shipped in open
position.
Fig. 6-1
Connecting a wire
Instructions:
a) Use appropriate copper cables that are designed for
minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation
regulations!
c) Ensure that all strands of a stranded wire enter the terminal
connection!
d) Ferrules are allowed, but not required.
e) Do not connect or disconnect the wires from the terminals
below -25°C (-13°F).