Lifetime Expectancy and 
Mean Time Between Failure

The redundancy module has two input channels, which are completely 
independent from each other. The dual-input redundancy module can be 
considered as two single redundancy modules combined in one housing. The 
only common point is the circuit trace that ties the two separate circuits 
together at the output.

The Mean Time Between Failure (MTBF) values in the following table are for 
the entire dual-input module. If you need the MTBF number of only one path, 
double the value from the table.

Terminals and Wiring

The terminals are IP20 fingersafe constructed and suitable for field wiring and 
factory wiring.

Wiring rules:

Use appropriate copper cables that are designed for minimum operating 
temperatures of: 
- 75 °C (167 °F) for ambient up to 55 °C (131 °F)
- 90 °C (194 °F) for ambient up to 70 °C (158 °F)

Follow national installation codes and installation regulations.

Ensure that all strands of a stranded wire enter the terminal connection.

Unused terminal compartments should be securely tightened.

Ferrules are allowed.

Input / Output Current Conditions

N+1 Redundancy
Input: 2 x 10 A 
Output: 20 A

1+1 Redundancy
Input: 2 x 5 A 
Output: 10 A

Notes

Lifetime expectancy

(1)

Min

113,000 h

309,000 h

at 24V and 40 °C (104 °F)

Min

320,000 h

874,000 h

at 24V and 25 °C (77 °F)

MTBF

(2)

 

SN 29500, IEC 61709

7,837,000 h

20,310,000 h

at 24V 40 °C (104 °F)

19,408,000 h

46,382,000 h

at 24V 25 °C (77 °F)

MTBF 

(2)

 

MIL HDBK 217F

1,774,000 h

1,817,000 h

at 24V and 40 °C (104 °F) (Ground Fixed GF40)

2,709,000 h

2,782,000 h

at 24V and 25 °C (77 °F) (Ground Fixed GF25)

3,675,000 h

3,707,000 h

at 24V and 40 °C (104 °F) (Ground Benign GB40)

5,620,000 h

5,674,000 h

at 24V and 25 °C (77 °F) (Ground Benign GB25)

(1)

The Lifetime expectancy values that are shown in the table indicate the minimum operating hours (service life) and are determined by the 
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to 
the manufacturer specification of the capacitor. The manufacturer of the electrolytic capacitors only states a maximum life of up to 15 years 
(131,400 h). Any number that exceeds this value is a calculated theoretical lifetime, which can be used to compare devices.

(2) Mean Time Between Failure (MTBF) is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical 

representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. The MTBF value is a statistical 
representation of the likelihood of a device to fail. An MTBF value of, for example, 1,000,000 h means that statistically one unit fails every 100 
hours if 10,000 units are installed in the field. However, it cannot be determined if the failed unit has been running for 50,000 h or only for 100 h.

Attributes

Values and Descriptions

Type

screw terminals

Solid wire

6 mm

2

 max

Stranded wire

4 mm

2

 max

American Wire Gauge

AWG20…10

Wire diameter max

2.8 mm (0.110 in.) (including ferrules)

Wire stripping length

7 mm (0.28 in.)

Screwdriver

3.5 mm (0.138 in.) slotted or cross-head No 2

Recommended tightening torque

1 N•m, 9 lb•in

Summary of Contents for 1606-XLBRED20

Page 1: ...DualInputRedundancyModule DC 12 28V 20 A Catalog Number 1606 XLBRED20 Reference Manual Original Instructions...

Page 2: ...kwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permissi...

Page 3: ...Diagram 9 Front Side and User Elements 9 Electromagnetic Compatibility 10 Environment 11 Protection Features 11 Safety Features 12 Dielectric Strength 12 Approvals 12 Standards 12 Physical Dimensions...

Page 4: ...4 Rockwell Automation Publication 1606 RM111A EN P July 2020 Notes...

Page 5: ...most failures in a single power supply The two power supply outputs should be isolated from each other by using diodes or other switching arrangements For example two 10 A power supplies are needed t...

Page 6: ...can cause controller failures Product features Cost effective solution to build redundant systems Dual input with single output Two diodes common cathode DC 12 28V 25 wide range input Full power from...

Page 7: ...of the power sources and if the power source can deliver more than 26 A together use an appropriate fuse on the output at continuous overload or short circuit Reverse current Max 4 mA per input 40 70...

Page 8: ...817 000 h at 24V and 40 C 104 F Ground Fixed GF40 2 709 000 h 2 782 000 h at 24V and 25 C 77 F Ground Fixed GF25 3 675 000 h 3 707 000 h at 24V and 40 C 104 F Ground Benign GB40 5 620 000 h 5 674 000...

Page 9: ...tional Diagram Figure 6 Functional Diagram Front Side and User Elements Input 1 Input 2 Output Surge Protection Surge Protection Surge Protection Figure 7 Front Side User Elements 1 Input terminals fo...

Page 10: ...on A earthed DIN rail 1 kV Criterion A Conducted disturbance on input lines EN 61000 4 6 0 15 80 MHz 20V Criterion A Conducted disturbance on output lines EN 61000 4 6 0 15 80 MHz 20V Criterion A Powe...

Page 11: ...ne or other LABS critical substances and is suitable for use in paint shops 1 Operational temperature is the same as the ambient temperature and is defined as the air temperature 2 cm 0 79 in below th...

Page 12: ...ndicates conformance with the EMC Directive IEC 60950 1 CB Scheme Information Technology Equipment UL 508 Listed for use as Industrial Control Equipment U S A UL 508 and Canada C22 2 No 107 1 01 E Fil...

Page 13: ...ht of 7 5 mm 0 295 in or 15 mm 0 59 in Plastic Material of Housing Flame retardant Polycarbonate PC UL94 V0 Vicat softening temperature specified with 149 C 300 F according to ASTM D1525 Installation...

Page 14: ...e separate input fuses for each power supply Set the power supply in Parallel Use mode if this feature is available It is desirable to set the output voltages of all power supplies to the same value I...

Page 15: ...sensitive loads as shown in Figure 14 With the 1606 XLBRED20 redundancy module the power supply for the demanding loads can be used as a redundant source to supply the controls as shown in Figure 15...

Page 16: ...Redundancy up to 20 A requires two 20 A power supplies and two 1606 XLBRED20 redundancy modules Use separate mains systems for each power supply whenever it is possible The power supply in Figure 16...

Page 17: ...res and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application Instal...

Page 18: ...owledgebase Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find instal...

Reviews: