Allen-Bradley 1606-XLBRED20 Reference Manual Download Page 10

10

Rockwell Automation Publication 1606-RM111A-EN-P - July 2020

           

Electromagnetic 
Compatibility

The redundancy module is suitable for applications in industrial, residential, 
commercial, and light industrial environments without any restrictions.

The following table shows electromagnetic compatibility (EMC) immunity 
according to generic standards EN 61000-6-1 and EN 61000-6-2.

The following table shows EMC emission according to generic standards 
EN 61000-6-3 and EN 61000-6-4. The redundancy module incorporates only 
diodes and no RF-generating circuits and does not contribute to EMC 
emissions.

Attributes

Standards

Values

Criteria

(1)

Electrostatic discharge

EN 61000-4-2

Contact discharge
on indirect coupling plane

8 kV

Criterion A

Air discharge

15 kV

Criterion A

Electromagnetic RF field

EN 61000-4-3

80 MHz…2.7 GHz

20V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

Input lines 

2 kV 

Criterion A 

Output lines 

2 kV

Criterion A

Surge voltage on input lines

EN 61000-4-5

 

-

500V

Criterion A

+/

 

earthed DIN rail

1 kV

Criterion A

Surge voltage on output lines

EN 61000-4-5

 

-

500V

Criterion A

+/

 

earthed DIN rail

1 kV

Criterion A

Conducted disturbance on input lines

EN 61000-4-6

0.15…80 MHz

20V

Criterion A

Conducted disturbance on output lines

EN 61000-4-6

0.15…80 MHz

20V

Criterion A

Power-frequency magnetic field

(2)

EN 61000-4-8

50 Hz

30 A/m

Criterion A

(1)

Criteria A: Redundancy module shows normal operation behavior within the defined limits.

(2) A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields, 

for example hall elements and electrodynamic microphones.

Attributes

Standards

Notes

Conducted emission input lines

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

limits for DC power ports according to EN 61000-6-3 fulfilled

(1)

 

(2)

Conducted emission output lines

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

limits for DC power ports according to EN 61000-6-3 fulfilled

(1)

 

(2)

Radiated emission

EN 55011, EN 55022

Class B

(2)

This device complies with FCC Part 15 rules.
Operation is subjected to the following two conditions: 1. This device may not cause harmful interference. 2. This device must accept any 
interference received, including interference that may cause undesired operation.

(1)

For information only, not mandatory for EN 61000-6-3.

(2) if power sources that are connected on the inputs fulfill the requirements too.

Summary of Contents for 1606-XLBRED20

Page 1: ...DualInputRedundancyModule DC 12 28V 20 A Catalog Number 1606 XLBRED20 Reference Manual Original Instructions...

Page 2: ...kwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permissi...

Page 3: ...Diagram 9 Front Side and User Elements 9 Electromagnetic Compatibility 10 Environment 11 Protection Features 11 Safety Features 12 Dielectric Strength 12 Approvals 12 Standards 12 Physical Dimensions...

Page 4: ...4 Rockwell Automation Publication 1606 RM111A EN P July 2020 Notes...

Page 5: ...most failures in a single power supply The two power supply outputs should be isolated from each other by using diodes or other switching arrangements For example two 10 A power supplies are needed t...

Page 6: ...can cause controller failures Product features Cost effective solution to build redundant systems Dual input with single output Two diodes common cathode DC 12 28V 25 wide range input Full power from...

Page 7: ...of the power sources and if the power source can deliver more than 26 A together use an appropriate fuse on the output at continuous overload or short circuit Reverse current Max 4 mA per input 40 70...

Page 8: ...817 000 h at 24V and 40 C 104 F Ground Fixed GF40 2 709 000 h 2 782 000 h at 24V and 25 C 77 F Ground Fixed GF25 3 675 000 h 3 707 000 h at 24V and 40 C 104 F Ground Benign GB40 5 620 000 h 5 674 000...

Page 9: ...tional Diagram Figure 6 Functional Diagram Front Side and User Elements Input 1 Input 2 Output Surge Protection Surge Protection Surge Protection Figure 7 Front Side User Elements 1 Input terminals fo...

Page 10: ...on A earthed DIN rail 1 kV Criterion A Conducted disturbance on input lines EN 61000 4 6 0 15 80 MHz 20V Criterion A Conducted disturbance on output lines EN 61000 4 6 0 15 80 MHz 20V Criterion A Powe...

Page 11: ...ne or other LABS critical substances and is suitable for use in paint shops 1 Operational temperature is the same as the ambient temperature and is defined as the air temperature 2 cm 0 79 in below th...

Page 12: ...ndicates conformance with the EMC Directive IEC 60950 1 CB Scheme Information Technology Equipment UL 508 Listed for use as Industrial Control Equipment U S A UL 508 and Canada C22 2 No 107 1 01 E Fil...

Page 13: ...ht of 7 5 mm 0 295 in or 15 mm 0 59 in Plastic Material of Housing Flame retardant Polycarbonate PC UL94 V0 Vicat softening temperature specified with 149 C 300 F according to ASTM D1525 Installation...

Page 14: ...e separate input fuses for each power supply Set the power supply in Parallel Use mode if this feature is available It is desirable to set the output voltages of all power supplies to the same value I...

Page 15: ...sensitive loads as shown in Figure 14 With the 1606 XLBRED20 redundancy module the power supply for the demanding loads can be used as a redundant source to supply the controls as shown in Figure 15...

Page 16: ...Redundancy up to 20 A requires two 20 A power supplies and two 1606 XLBRED20 redundancy modules Use separate mains systems for each power supply whenever it is possible The power supply in Figure 16...

Page 17: ...res and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application Instal...

Page 18: ...owledgebase Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find instal...

Reviews: