10
Rockwell Automation Publication 1606-RM111A-EN-P - July 2020
Electromagnetic
Compatibility
The redundancy module is suitable for applications in industrial, residential,
commercial, and light industrial environments without any restrictions.
The following table shows electromagnetic compatibility (EMC) immunity
according to generic standards EN 61000-6-1 and EN 61000-6-2.
The following table shows EMC emission according to generic standards
EN 61000-6-3 and EN 61000-6-4. The redundancy module incorporates only
diodes and no RF-generating circuits and does not contribute to EMC
emissions.
Attributes
Standards
Values
Criteria
(1)
Electrostatic discharge
EN 61000-4-2
Contact discharge
on indirect coupling plane
8 kV
Criterion A
Air discharge
15 kV
Criterion A
Electromagnetic RF field
EN 61000-4-3
80 MHz…2.7 GHz
20V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines
2 kV
Criterion A
Output lines
2 kV
Criterion A
Surge voltage on input lines
EN 61000-4-5
+
-
500V
Criterion A
+/
-
earthed DIN rail
1 kV
Criterion A
Surge voltage on output lines
EN 61000-4-5
+
-
500V
Criterion A
+/
-
earthed DIN rail
1 kV
Criterion A
Conducted disturbance on input lines
EN 61000-4-6
0.15…80 MHz
20V
Criterion A
Conducted disturbance on output lines
EN 61000-4-6
0.15…80 MHz
20V
Criterion A
Power-frequency magnetic field
(2)
EN 61000-4-8
50 Hz
30 A/m
Criterion A
(1)
Criteria A: Redundancy module shows normal operation behavior within the defined limits.
(2) A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields,
for example hall elements and electrodynamic microphones.
Attributes
Standards
Notes
Conducted emission input lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
limits for DC power ports according to EN 61000-6-3 fulfilled
(1)
Conducted emission output lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
limits for DC power ports according to EN 61000-6-3 fulfilled
(2)
Radiated emission
EN 55011, EN 55022
Class B
This device complies with FCC Part 15 rules.
Operation is subjected to the following two conditions: 1. This device may not cause harmful interference. 2. This device must accept any
interference received, including interference that may cause undesired operation.
(1)
For information only, not mandatory for EN 61000-6-3.
(2) if power sources that are connected on the inputs fulfill the requirements too.