background image

 

Rockwell Automation Support 

For Technical Support, visit ROK.AUTO/SUPPORT. 

The information in this document is believed to be accurate and reliable and may change without notice.

 

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. 
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their companies. 

www.rockwellautomation.com 

Power, Control and Information Solution Headquarters 

Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax. (1) 414.382.4444 
Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgien, Tel: (32) 2663.0600, Fax (32) 2663.0640 
Asia Pacific: Rockwell Automation,Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887.4778, Fax (852) 2508.1846 
Turkey: Rockwell Otomasyon Ticraet A.

Ş

., Kar Plaza 

İş

 Merkezi E Blok Kat:6 34752 

İ

çerenköy, Istanbul, Tel: (90) 216.5698400  (EEE Yönetmeli

ğ

ine Uygundur)

 

Publication 1606-IN059A-EN-E - June 2020

 

DIR 10005140931 (Version 01)

Copyright © 2020 Rockwell Automation, Inc. All Rights Reserved..

 

The device is designed for pollution degree 2 areas in controlled environments. No condensation or frost is 
allowed. 
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide protection 
against spilled liquids. 
The isolation of the device is designed to withstand impulse voltages of overvoltage category III according to IEC 
60664-1. 
The device is designed as “Class of Protection” I equipment according to IEC 61140. Do not use without a proper 
PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage between the 
input terminal and the PE potential must not exceed 300Vac. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and 
do not cover ventilation grid! 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) the overvoltage category is 
reduced to level II and a reduction in output current is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 0mm left and right side. 
Increase the 0mm to 15mm in case the adjacent device is a heat source. 
The device is designed, tested and approved for branch circuits up to 20A without additional protection device. If 
an external fuse is utilized, do not use circuit breakers smaller than 6A B- or 4A C-Characteristic to avoid a 
nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the 
ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any kind of loads, 
including inductive and capacitive loads. Capacitive loads should not be larger than 2500µF with 2.5A or 5000µF 

with 1.25A additional current load. 
Do not apply return voltages from the load to the output terminals higher than 35V. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC-OK LED reports an output voltage above 18V of a running device. 
At heavy overloads (when output voltage falls below 14V), the device delivers continuous output current for 25ms. 
After this, the output is switched off for 145ms before a new start attempt is automatically performed. This cycle is 

repeated as long as the overload exists. 
Do not parallel devices for higher output currents. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many outputs in 
series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32V. The output shuts 
down. To attempt a restart, turn the input power off for at least 90s. 

 

Functional Diagram 

Input

Fuse

&

Input

Filter

L

N

Output Over-

Voltage

Protection

Input

Rectifier

&

Inrush

Limiter

Output

Voltage

Regulator

+

+

-

-

Output

Filter

V

OUT

DC-ok

LED

Power

Converter

 

 

Output Characteristic 

Output voltage

6A

24V

Output current

14V

0V

2A

5A

0A

Adjustment range

28V

A

B

1A

3A

A: continuous current

B: intermittent current

4A

 

 

Temperature Range 

Allowed output current at 24V

Ambient temperature

0A

-10

A: continuous

B: short term (max. 60s)

2.5A

+60

+70°C

1.9A

A

B

 

 

Reviews: