
10
Rockwell Automation Publication 1606-RM104A-EN-P - July 2020
Hold-up Time
The hold-up time is the time during which output voltage of a power supply
remains within specification following the loss of input power. The hold-up
time is output load dependent. At no load, the hold-up time can be up to
several seconds. The green DC OK lamp is also on during this time.
DC OK Relay Contact
This feature monitors the output voltage on the output terminals of a running
power supply.
Figure 11 - DC OK relay contact behavior
Type and Conditions
AC 100V
AC 120V
AC 230V
References
Hold-up time
Typ at 24V, 10 A
54 ms
54 ms
54 ms
Min at 24V, 10 A
44 ms
44 ms
44 ms
Typ at 24V, 20 A
27 ms
27 ms
27 ms
Min at 24V, 20 A
22 ms
22 ms
22 ms
Figure 9 - Hold-up time vs. input voltage
Figure 10 - Shut-down behavior, definitions
0
10
20
30
60 ms
85
120
155
190
230V AC
Input Voltage
40
50
Hold-up Time
24V, 20 A, typ.
24V, 10 A, min.
24V, 10 A, typ.
24V, 20 A, min.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
Attributes
Descriptions
Contact closes
As soon as the output voltage reaches 22V.
Contact opens
As soon as the output voltage falls below 22V.
Switching
hysteresis
0.3V typ
Contact ratings
Maximal 60V DC 0.3 A, 30V DC 1 A, 30V AC 0.5 A, resistive load
Minimal permissible load: 1 mA at 5V DC
Isolation voltage
See dielectric strength table in
Dielectric Strength on page 17
22V
open
Output Voltage
closed