20
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Basic Power Supply 10 A
Environment
Attribute
1606-XLB240E
Notes
Operational temperature
(1)
-25… +70 °C (14...158 °F)
reduce output power, see
Figure 21
.
Storage temperature
-40… +85°C (-40…185 °F)
for storage and transportation
Output derating
6W/°C
50°…70 °C (131…158 °F)
Humidity
(2)
5...95% r.h.
IEC 60068-2-30
Vibration sinusoidal
(3)
2…17.8 Hz: ±1.6 mm (0.06 in.);
17.8…500Hz: 2 g 2 hours/axis
IEC 60068-2-6
Shock
(4)
30 g 6ms, 20 g 111ms
3 bumps/direction, 18 bumps in total
IEC 60068-2-27
Altitude
0…2000 m (0…6 560 ft)
without any restrictions
2000…6000 m (6 560… 20,000 ft)
reduce output power or ambient temperature,
see
Figure 22
. IEC 62103, EN 50178,
overvoltage category II
Altitude derating
15 W/1000 m or 5 °C/1000 m
> 2000 m (6500 ft), see
Figure 22
.
Overvoltage category
III
IEC 62103, EN 50178, altitudes up to 2000 m
II
altitudes from 2000 m to 6000 m
Degree of pollution
2
IEC 62103, EN 50178, not conductive
LABS compatibility
The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
(1) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2 cm (0.79 in.)
below the unit.
(2) Do not energize while condensation is present.
(3) Tested on a DIN Rail with a thickness of 1.3 mm (0.05 in.)
(4) Tested on a DIN Rail with a thickness of 1.3 mm (0.05 in.)
Figure 21 - Output Current vs. Ambient Temperature
Figure 22 - Output Current vs. Altitude
0
-10
0
+20
+40
+70°C
2.5A
5.0A
7.5A
10A
+55
Allowable Output Current at 24V
6.3A
Ambient Temperature
-25
Allowed Output
Current at 24V
0
0
2000
4000
6000m
2A
4A
6A
8A
10A
12A
Altitude
A... Tamb < 55°C
B... Tamb < 45°C
C... Tamb < 35°C
A
B
C