10
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Basic Power Supply 10 A
Output
Attribute
1606-XLB240E
Notes
Output voltage
nom
DC 24V
Adjustment range
24…28V
guaranteed
30V
(1)
at clockwise end position of potentiometer
Factory settings
typ
24.1V
±0.2%, at full load, cold unit
Line regulation
max
5 mV
90…264V AC
Load regulation
max
100 mV
static value, 0A .. 10A, see
Figure 7
Ripple and noise voltage
max
100 mVpp
20 hz to 20 MHz, 50 Ohm
Output current
nom
10 A
at 24V, below +55 °C (131 ° F) ambient temperature
6.25 A
at 28V, below +55 °C (131 ° F) ambient temperature
8.6 A
at 24V, at +70 °C (158 ° F) ambient temperature
5.4 A
at 28V, at +70 °C (158 ° F) ambient temperature
Output power
nom
240 W
ambient temperature < 55 ° C (131 ° F)
150 W
ambient temperature < 70 °C (158 ° F)
Overload behavior
continuous current
output voltage > 13V DC, see
Figure 7
Hiccup
PLUS
mode
output voltage < 13V DC, see
Figure 7
Short circuit current
min
11 A
(2)
load impedance 50mOhm, see
Figure 7
max
15 A
load impedance 50mOhm, see
Figure 7
typ
4.8 A
(3)
average (R.M.S.) current, load impedance 50 mOhm, see
Figure 7
Output capacitance
typ
2 850 μF
included inside the power supply
(1) This is the maximum output voltage that can occur at the clockwise end position of the potentiometer due to tolerances. It is not a guaranteed value that can be achieved. The typical value is
about 28.5V.
(2) Discharge current of output capacitors is not included.
(3) Discharge current of output capacitors is not included.
Figure 7 - Output Voltage vs. Output Current, typ
Figure 8 - Short circuit (50 mOhm) on output, Hiccup
Output Voltage
0
0
12.5
4
8
12
28V
16
20
24
15A
7.5
2.5
5
10
Adjustment
Range
Output Current
Continuous
current
Hiccup
PLUS
mode
Output
Current
0
13.5A
7s
7s
7s
1s
1s
3s
t
Short -circuit
Normal
operation
Normal
operation
First
pulse: 3s