Publication 1404-UM001D-EN-E - October 2004
Data Logging
7-5
Reading Data from the Event Log Using Communications
The Event Log uses the indexed read method. Table A.26 is the
Read-back Select
table and Table A.27 is the
Results
table. You may
select among a number of read-back options for the Event Log:
0 = Auto-increment / start at beginning of log
1 = Auto-increment / start at end of log
2 = Auto-decrement / start at end of log
3 = Point to the beginning of log
4 = Point to the end of log
5 = Index to the next record
6 = Index to the previous record
Indexing occurs after each read of the
Results
table.
Only mode 0, 1 and 2 are supported by DF1 and Remote I/O
communications.
Table A.27 is a read-only data table containing 14 (M4, M5), 17 (M6)
or 18 (M8 only) integer elements as follows:
•
Reserved:
returns 0
•
Event record internal identifier:
An incremental number
assigned to each new event. See below
•
Timestamp:
event timestamp expressed in four-element
timestamp format (see below)
•
Event type:
see Table 7.1
•
Event command code:
•
Setpoint type, evaluation condition, level, action/release delay,
and action:
if event is a setpoint, these elements return
additional information about the setpoint. The
Setpoint level
,
expressed in integer/exponent format, records the worst-case
value of the setpoint parameter
•
Sustain limit timer (M6, M8 only):
time the setpoint parameter
exceeded the limit, expressed in integer/exponent format
•
Capture identifier (M6, M8 only):
identifies oscillograph or
transient capture number if applicable
•
Event text available (M8 only):
0 indicates no user comment; 1
indicates a user comment has been stored in the current record
(see below)
Summary of Contents for 1404-M4
Page 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Page 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Page 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Page 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Page 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Page 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Page 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Page 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Page 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Page 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Page 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Page 355: ...Allen Bradley HMIs ...