background image

4

1397 I/O Expansion Card

1397 – 5.19     August, 2000

Installation
Requirements

(continued)

Retaining

Screw

Retaining

Screw

Retaining

Screw

Retaining

Screw

Carrier Shield

3

To remove the carrier shield, remove
the (4) retaining screws and unplug the
ground wire at the Power Supply
Board.

Power
Supply
Board

J17

Connector

J17

Carrier Shield

Summary of Contents for 1397-L11

Page 1: ...Input 1 Frequency Output These I O signals are configured and programmed by 5 jumpers and 27 parameters detailed in the Setup section Where This Option Is Used This option may be used with all 1397 Drives What These Instructions Contain These instructions contain the necessary information to install and configure a 1397 I O Expansion Card For additional information on I O signals cable and wire re...

Page 2: ...V DC 0 1 3kΩ Max Load 4 20mA Output Analog Output 4 External Supply 10V DC Max Load 4mA Frequency Input Max Frequency 250kHz Min Duty Cycle 25 at 250kHz 20 at 100kHz Time On to Time Off Min Pulse Width 2µS Input Differential A and A Input Voltage 50V Maximum Differential 25V to Common 1 5V Min Differential Voltage Swing Input Impedance 22kΩ Differential 11kΩ to Isolated 15V Common Signal Common 10...

Page 3: ...protection handbook Captive Thumb Screw Captive Thumb Screw 1 Remove and lock out all incoming power to the drive Loosen the 2 captive retaining screws and remove the drive cover 2 Loosen the captive carrier retaining screw and swing the carrier door open Captive Carrier Screw ATTENTION Electric Shock can cause injury or death Remove all power before working on this product The drive is at line vo...

Page 4: ...quirements continued Retaining Screw Retaining Screw Retaining Screw Retaining Screw Carrier Shield 3 To remove the carrier shield remove the 4 retaining screws and unplug the ground wire at the Power Supply Board Power Supply Board J17 Connector J17 Carrier Shield ...

Page 5: ...38 39 39 40 40 41 41 42 42 43 43 44 44 50 50 51 51 52 52 53 53 54 ANALOG OUTPUT 1 J14 M A V 54 55 55 56 56 57 57 58 58 59 59 60 60 61 61 62 62 63 63 64 64 65 65 66 66 67 67 68 68 69 69 68 68 69 69 IOUT SOURCE INT EXT J15 J11 J12 14 20 PARK VOLTS V MA ANALOG INPUT J5 J6 J7 J8 J9 J10 J1 74 74 75 75 76 76 71 71 72 72 73 73 J6 J5 15V A COM ANOT B BNOT 15V A COM ANOT B BNOT J2 J1 Pulse Encoder Interfac...

Page 6: ... 1 5 J 1 2 4 2 0 P A R K V O L T S V M A A N A L O G I N P U T 1 J 5 J 6 J 2 J 1 J 1 0 3 3 3 4 38 39 40 41 42 43 44 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 J 1 4 M A V J11 Jumpers Jumper J12 Aux Pot Terminal Block J10 Wiring Specifications 5 terminal blocks are available for I O connections to the I O Expansion Card Refer to the Cable and Wire Recommendations in the 1397 User M...

Page 7: ...1 1 No Change Terminal 64 2 OCL Enable Turns Outer Control Loop OCL on or off based on the drive s running state and P 121 OCL Enable Src 5 1 For a detailed description of these Digital Input Parameters refer to the parameter descriptions in the 1397 User manual 2 Depending upon the application terminal 58 24VDC 61 24VDC or 65 24V COM is used with this digital input terminal 3 Refer to the Speed T...

Page 8: ...nalog Input Parameters refer to the parameter descriptions in the 1397 User manual 53 54 55 56 57 59 60 61 62 58 J6 J5 38 39 40 41 42 43 44 50 51 52 A n l g I n 3 A n l g I n 4 A n l g I n 4 A n l g I n 3 Setup continued D i g O u t 1 C o m D i g O u t 2 D i g O u t 2 C o m D i g O u t 1 66 67 68 69 J9 J8 Digital Output Jumper and Parameter Settings To configure the I O Expansion Cards digital out...

Page 9: ...1 4 20 PARK J12 Set for 4 20mA Input 4 For A 4 20mA Input Set analog input jumpers J11 to mA and J12 to 4 20 Park Setup continued M A J11 Set for Amps A N A L O G I N P U T 1 1 0 5 0 J12 Set for 10 50mA Input 5 For A 10 50mA Input Set analog input jumpers J11 to mA and J12 to Volts 10 50mA V J11 Set for Volts A N A L O G I N P U T 1 PARK VOLTS J12 Set for Volts 3 For A Bipolar or Unipolar DC Input...

Page 10: ...Terminal Nos P 151 Anlg Out 3 SRC 54 and 55 2 3 4 5 P 150 Anlg Out 3 Gain P 154 Anlg Out 4 SRC 56 and 57 1 P 153 Anlg Out 4 Gain 1 For a detailed description of these Analog Output Parameters refer to the parameter descriptions in the 1397 User manual 53 54 55 56 57 59 60 61 62 58 J6 A n l g O u t 3 A n l g O u t 4 A n l g O u t 4 A n l g O u t 3 Setup continued J14 Set for Volts A N A L O G O U T...

Page 11: ...ipolar frequency output only parameters 1 must be set The output signal is unfiltered and read every 20mS The full scale value is based on their selected parameter group Load Speed Voltage Power Field or other Parameter No Parameter Name Terminal Nos P 160 Freq Out SRC 42 43 and 44 P 161 Freq Out Zero P 159 Freq Out Scale 38 39 40 41 42 44 50 51 52 43 J5 F r e q O u t A C o m F r e q O u t A 5 Wir...

Page 12: ...Publication 1397 5 19 August 2000 P N 184659 02 Supersedes November 1996 Copyright 2000 Rockwell International Corporation All rights reserved Printed in USA ...