10
1397 I/O Expansion Card
1397 – 5.19 August, 2000
Analog Output Settings
The I/O Expansion Card supports two analog outputs — Anlg Out 3
and Anlg Out 4. Both I/O Expansion Card outputs are unfiltered,
where as standard analog outputs are averaged.
Anlg Out 3 has (2) parameter settings
1
and can be jumpered to supply
(2) types of output signals.
Anlg Out 4 has (2) parameter settings
1
and can only supply a bipolar
DC voltage.
Analog outputs can be scaled to supply DC voltage signals as low as
5V DC, but the maximum resolution of 0.025% is only obtained when
a full scale output signal is used. Analog outputs are updated every
20mS.
Parameter No.
Parameter Name
Terminal Nos.
P.151
Anlg Out 3 SRC
54 and 55
2, 3, 4, 5
P.150
Anlg Out 3 Gain
P.154
Anlg Out 4 SRC
56 and 57
1
P.153
Anlg Out 4 Gain
1
For a detailed description of these Analog Output Parameters, refer to the parameter
descriptions in the 1397 User manual.
53
54 55
56
57
59
60
61
62
58
J6
Anlg Out 3
–
Anlg Out 4 +
Anlg Out 4
–
Anlg Out 3 +
Setup
(continued)
J14
Set f
or
Volts
ANALOG
OUTPUT 1
V
2
For A Bipolar DC Output Voltage
— Set analog output jumper J14 to V.
J14
Set f
or
Amps
J15
Set f
or
4-20mA Output
Internal Sour
ce
ANALOG
OUTPUT 1
M
A
IOUT
SOURCE
IN
T
3
For A 4-20mA Output Internal Source
— Set analog output jumpers J14 to mA and J15 to INT.
J14
Set f
or
Amps
J15
Set f
or
4-20mA Output
External Sour
ce
ANALOG
OUTPUT 1
MA
IOUT
SOURCE
EX
T
4