All Security Equipment ASE-KP1000EGRESS Programming & Installation Manual Download Page 7

8  0 

8  0 

1-999 sec 

Door Forced Open Alarm is Activated 
Door Forced Open Alarm is Disabled 

7  2

7  2

Notification beep disabled and replaced by 2 

short successful code entry beeps for valid 

user codes. 

 

 

E)  Door Forced Open Alarm – Installer Programming  

  

       Locations   Function Code  

Validation   Comments 

 

 

 

 

F) Out put  Act ivat ion Annunciat ion – Installer Programming  

 

Locations   Function Code  

Validation   Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7  1 

7  1 

7  0 

Auto Entry Mode is selected.        Key that follows 

the user code is not  required in code entry. The user 

codes must be set in the same  digit length as the 

Master Code in Auto Entry mode and the code can be 

4-8 digits 

7 0

Manual Entry Mode is selected.       Key that follows 

the user code is required in  code entry. The user codes 

can be 4-8 digits and are not required to be the same 

length as the Master Code. 

Tones are active on key press 

Tones are off. Use for silent environment requirements

NOTE: 

In single user mode, if selection is auto or manual  mode, the Master Code and the User Code must be set 

to 4 digits length. 

G) User Code Ent ry Mode (Aut o or Manual) – Installer Programming  

 

Locations   Function Code  

Validation   Comments 

 

 

 

 

 

 

 

 

 

 

 

 

H)  Pacifier Tones (Key-press Acknowledgement  Tones) – Installer Programming  

 

Locations   Function Code  

Validation   Comments 

 

 

 

 

8

No Propped Open Alarm 

Time from 1 to 999 seconds until door 

propped open activates alar m

 

1 to 999 

 

I)  Door Propped Open Alarm Time – Installer Programming  

 

Locations   Function Code  

Validation   Comments 

 

 

 

 

 

 

(system default)

(system default)

(system default)

(system default)

(system default)

1 second notification beep is given to notify the 

person outside to open the door when output relay is 

activated with a user code or egress button.  Good for 

the locking device that gives no sound when it 

activates, such as a magnetic lock.

Summary of Contents for ASE-KP1000EGRESS

Page 1: ...VANDAL RESISTANT DIGITAL KEYPAD WITH DELAYED EGRESS FEATURE AND 1000 USER CODES Post Mount Keypad Programming Installation Manual...

Page 2: ...digits and To program Relay 1 users 6 To set USER CODE 1 Press 102 then 001 and 4 digits and 7 To set USER CODE 2 Press 102 then 002 and 4 digits and 8 To set USER CODE 3 Press 102 then 003 and 4 digi...

Page 3: ...ck mounts or on posts and walls TERMINAL CONNECTIONS FOR THE POST MOUNT KEYPAD 12 24V AC DC POWER INPUT Connect to 12 24V AC or DC power supply The supply and GND are the common grounding points of th...

Page 4: ...o turn on lights CCTV camera or buzzers to notify a guard This output is rated at I c max 100mA sink V c max 24VDC DU OUT Duress Output is an NPN open collector output transistor that switches to grou...

Page 5: ...tion time While one of the doors in the system is opened the other doors keeps closed until the first door is closed to prevent unauthorized people dashing into a protected area N C TAMPER Normally Cl...

Page 6: ...on Comments 5 1 5 1 0 5 2 1 to 999 From 1 to 999 seconds default is 5 seconds Output 1 in Start Stop Mode toggle Output 1 in Start Stop Mode toggle with accelerated code 5 2 5 2 0 1 to 999 Output 2 in...

Page 7: ...e same length as the Master Code Tones are active on key press Tones are off Use for silent environment requirements NOTE In single user mode if selection is auto or manual mode the Master Code and th...

Page 8: ...ation Visitor ID Valid Period 4 digit code Visitor Code Codes not valid after one use or time expires Validation MASTER CODE Programming and use of t he keypad Operation Examples A Programming Procedu...

Page 9: ...2 1 1 0 2 0 0 2 6 8 5 4 5 1 1 0 5 2 6 0 1 0 System has been placed in program mode with factory set Master Code System has been set for Single User Mode see note a below 3289 has been stored as the n...

Page 10: ...Enter false codes into the keypad to test the security The keypad considers 4 digits as 1 code and it generates 5 beeps for each unsuccessful entry The keypad will lock for 15 minutes after 10 unsucc...

Page 11: ...mming mode All changes are stored system is ready to use 8 3 2 1 Output 1 activates for 1 second 1 1 2 1 Output 1 activates for 1 second 3 3 2 2 Output 1 activates for 1 second 2 Programming Note a In...

Page 12: ...Output 1 as if User Code 1 has been used The Duress Code can always activate or deactivate in Start Stop mode Output 1 but cannot deactivate the Duress Output Only the User Code in Group 1 can reset...

Page 13: ...nt All weather IP 66 Operation Modes a Single User Mode Auto or Manual Code Entry b Multi User 100 user codes for output 1 user number 00 99 Auto or Manual Code Entry 10 user codes for output 2 user n...

Page 14: ...ith the lock terminals to absorb the back EMF to prevent damage to the keypad The 1N4004 is not required if the electric lock is AC operated To avoid Electro Static Discharge from interfering with the...

Page 15: ...operation of the electric lock at night or after office hours to prevent unauthorized access Set output 2 to Start Stop toggle Mode Program Option 51 for ON Off control Simply connect the output 1 in...

Page 16: ...s necessary to link up the GND terminals of the two keypads as common ground to achieve the inter lock logic function Use keypad to open door from outside Press egress button to open door from inside...

Page 17: ...Alarm The keypad will generate an alarm if the door is left open longer than the pre set time Enable the function with Program Option 9 with duration of 1 to 999 seconds With the help of a normally cl...

Page 18: ...17...

Page 19: ...en when activated N O Normally Open the contact is open circuit in a normal status It is closed when activated Transistor Open Collector Output An open collector output is equivalent to Normally Open...

Reviews: