All Seasons Hire Hot Block 25 Operating Instructions Download Page 4

Principles of Construction 

Electrical wiring diagrams are mounted inside the units. 
Remove the cover to refer. Units are built to IP.44 standards. 
The dual voltage (110/240v) version can be wired internally at 

a reduced capacity of 1.5kw on 110 volts. 
 
To alter the supply on the dual voltage unit, 110v to 240v, or 
vice versa, refer to the wiring diagram. 

 
Remember to rotate the supply identification plate on the top of 
the unit to match the appropriate wiring configuration for the 

dual voltage unit. Connecting the wrong supply to the unit can 
damage components and as such is not classed as a warranty 
fault. 
 

No neutral wire is required for the 415/3/50 units. Just 3 
phases and earth wires. 
 

The units are all supplied with carrying handles on the top 
cover. 
 

The top cover consists of the sides and top and is held in place 
by screws along the bottom of the sides. These screws are 
most easily removed using a socket spanner. 
 

The remainder of the "fixings" in the unit are rivets. Although 
we acknowledge this makes the exchange of parts potentially 
more difficult, as compared with the use of screws or bolts, 

experience has shown that any such exchanges are intermittent 
that the advantages of not having screws coming loose and/or 
them "seizing" over long periods, more than outweighs any 

disadvantage. 
 
 

 

 
 
 

Plugs and Cables 

Plugs and sockets have to be carefully selected to suit the 
capacity and voltage of the unit. 
The bare ends of the cable supplied with the heater are tinned. 

This is appropriate for connection into large terminal blocks. For 
smaller terminals, remove the length of tinning, leaving a short 
length of bare strands. 
 

Recommended Plugs 

Hot Block 25 

240 Volt 

13 Amp 3 Pin Plug 

 

 

 

 

 

16 Amp 2 Pole + E Industrial Plug 

Hot Block 25 

110 Volt 

32 Amp 2 Pole + E Industrial Plug 

Hot Block 65 

415 Volt 

32 Amp 3 Pole + E Industrial Plug 

Hot Block 95 

415 Volt 

32 Amp 3 Pole + E Industrial Plug 

 

The Hot Block 25 on a 110 volt supply requires a minimum of 

3kVA continuously rated transformer power. Any less 
transformer power reduce the heat output by reference to the 
wiring diagram inside the unit. 

 
For extended runs of supply cable, in excess of the cable 
supplied with the unit, the following schedule will allow for a 

maximum volt drop at the unit of 10 volts on maximum heat 
setting:- 

Hot Block 25 

110 Volt 

 

 

 

 

0 to 20 metres   

2.50mm² cables 

 

 

 

 

25 to 40 metres  

4.00mm² cables 

Hot Block 25 

240 Volt 

 

 

 

 

0 to 50 metres   

2.50mm² cables 

 

 

 

 

50 to 100 metres 

4.00mm² cables 

Hot Block 65 

415 Volt  

 

 

 

 

0 to 50 metres   

2.50mm² cables 

 

 

 

 

50 to 75 metres  

4.00mm² cables 

 

 

 

 

75 to 100 metres 

6.00mm² cables 

Hot Block 95 

415 Volt 

 

 

 

 

0 to 50 metres   

4.00mm² cables 

 

 

 

 

50 to 75 metres  

6.00mm² cables 

 

At the unit a voltage drop of more than 15% below the normal 
supply rating will cause damage to the heater. 

 